Select 6),

 

TACACS Encryption Enable

 

sets 

the encryption to off or on.  Sending 
unencrypted TACACS packets is useful for 
troubleshooting but should not be used under 
normal operations. 

TACACS encryption is..............Enabled
Enable ? (Y/N), CR for no change) : 

 

TACACS response timeout is   10 seconds

  Enter timeout, in seconds ( >=0 and <=30 )  
  0 = no timeout : 

TACACS server port is: 49 
Enter port number (>= 1024, D for default 49): 12 

TACACS Privilege Level is.........Disabled
 
  Enable ? (Y/N), CR for no change) : 

URPC Privilege Level is: 15 
Enter Privilege Level for root access: 

Select 7),

 

TACACS Login Timeout

 

sets the amount of time the unit will 
wait for a response from the TACACS 
server. 

Select 8),

 

TACACS Server Port

 

assigns 

a more secure port, 

default is TCP 49

. If 

you type a port number less than 1024 the 
Host Module responds with the same 
screen until a valid entry is typed. 

Select 9)

,

 URPC Privilege Level 

Enable

 

enables the unit to send a 

privilege level to the TACACS server. 

Default is Disabled

 

Select 10),

 

URPC Privilege Level

 

assigns privilege levels. 1 is the 
minimum user privilege and 15 is the 
root/admin privilege level.  

Default is 15

 

Example of operation:  Privilege Level enabled, set to “10”. In tacacs.conf file on daemon, user1 is 
configured for exec priv-lvl = 9, user2 is configured for exec priv-lvl = 10, and user3 is configured for 
exec priv-lvl = 11.  In this scenario, user1 will get only user-level access to the power strip, user2 & user3 
will get root access. 

TACACS User Privilege Feature 
Important:

 The TACACS admin user must perform the following before the TACACS Privilege level to 

operate: Open the tacacs.conf file and add the following entry for each user: (service = exec {priv-lvl = 
n}). Where “n” is a number from 1 to 15, inclusive. 15 is root privilege level, 1 is lowest level user.  “priv-
lvl” must be spelled exactly as shown, including case.  Restart the daemon after making changes. 

See Appendix: TACACS Connection: for troubleshooting connection problems with TACACS servers. 

Summary of Contents for ATS27

Page 1: ...Page 1 2019 COPYRIGHT 2019 Bay Technical Associates Inc 1 15 2019 ATS27 Transfer Switch ...

Page 2: ...hreshold 16 Change ATS Voltage Switching Points 16 Change ATS Switch Back Mode Time 16 Change ATS Delay Switch to Secondary 17 Change Buzzer Audible Alarms 18 Display Current Electrical Characteristics 19 Logging Out 19 Current User Password 19 Identify Current User 20 Unit Identification 20 Setting Source Input Primary 20 SETUP OPTIONS 20 RIPSET 20 NETWORK CONFIGURATION MENU 21 Status 21 Serial P...

Page 3: ...w Current Alarm Threshold 38 Environmental Sensors 39 Outlet Groups 40 Temperature Units degrees C F 41 Cascade Mode 42 Power Factor Threshold Menu 44 Firmware Config Download 48 Enable Firmware Upgrade 48 Enable SSL Cert Upload 48 Enable Configuration File Upload 49 Restore Configuration Defaults 49 Get Current Configuration File 50 Display Configuration Error Log 50 Enable Rel Ctl Firmware Upgra...

Page 4: ... dommages à l équipement IMPORTANT This term is used to denote conditions that could result in the loss of communications or to highlight the proper functioning of equipment IMPORTANT Ce terme est employé pour dénoter les conditions qui pourraient avoir comme conséquence la perte de communications ou accentuer le fonctionnement approprié de l équipement NOTE This term is used to denote items of in...

Page 5: ...odule has an RJ 45 port which uses an 8 pin crossed modular cable to connect to a local EIA 232 device such as a computer terminal or external modem Most serial computers do not have RJ 45 connections therefore an adapter is provided with this unit to convert from a DE 9 connector to an RJ 45 connector Bay Tech Part No 9FRJ45PC 4 An adapter to convert from a DB 25 connector to an RJ 45 connector i...

Page 6: ...ptacle L accès à l emplacement d installation devrait être limité au personnel autorisé L installation de ces unités devrait être limitée à ITE et à environnements de serveur de Telco CAUTION This unit is intended for indoor use only Do not install near water or expose this unit to moisture To prevent heat buildup do not coil the power cord when in use Do not use extension cords Do not attempt to ...

Page 7: ...nt et facilement accessible Les sorties fournissant la puissance à l unité seront protégées contre le courant le court circuit et le défaut de terre finis par les dispositifs protecteurs évalués appropriés 230 400V 32A 3 ØY Rated Model 32A Maximum Over current protection Devise 230 400V 16A 3 ØY Rated Model 16A Maximum Over current protection Devise 230 400V 24A 3 ØY Rated Model 30A Maximum Over c...

Page 8: ... 25 Pin Signal DTR 1 1 4 20 DSR GND 2 2 1 GND RTS 3 3 7 5 CTS TXD 4 4 3 2 RXD RXD 5 5 2 3 TXD DSR 6 N C 6 6 DTR GND 7 7 5 7 GND CTS 8 8 4 RTS DTR 4 DCD DCD 8 1 8 DTR RI 9 22 Depending on if the unit has circuit breakers in the case of power overload the circuit breaker automatically trips Determine the cause of the tripped circuit breaker correct the problem then reset the circuit breaker by depre...

Page 9: ... RJ45 to RJ45 Figure 2 RJ08X007 Pin Out Figure 3 RJ45 Connector Plug Adapters Figure 4 9FRJ45PC Cisco Adapter Pin Out Figure 5 9FRJ45PC 1 Adaptor Pin Out Use with RJ08X007 Cable And B C switch in C Use with RJ08X007 Cable And B C switch in B ...

Page 10: ...32 port to the adapter via the RJ08X007 rolled flat ribbon cable Use terminal emulation software to access the unit 9600 bps 8 data bits 1stop bit no parity no flow control and B C switch set to B NOTE At any time during the session you need to go to another menu use the Attention Character semi colon Press the attention character key 5 times to get back to the main status menu IMPORTANT If a devi...

Page 11: ...king cursor Type 5 semi colons there is a one second delay before the menu is displayed 5 You should get a Status menu similar to the one seen below ATS Series C 2014 Baytech F1 18 Option s Installed True RMS Voltage True RMS Current Internal Temperature Unit ID ATS Series Primary Source 1 Source 2 121 2 Volts Power True RMS Peak RMS True RMS Average Volt Source Current Current Voltage Power Amps ...

Page 12: ...list of commands ATS The Status Menu will display after the user logs in if a login is required This menu lists the firmware version installed options primary source secondary source voltage primary source current voltage and power and the internal temperature of the ATS unit If there are users installed on the unit a login will be required This may have a password or not It is recommended that at...

Page 13: ...isable Status Menu 4 Change Unit ID 5 Change Alarm Threshold 6 Change ATS Switching Voltage Points 7 Change ATS Switch Back mode time 8 Change ATS Delay Switch to secondary 9 Change Buzzer Audible Alarms X Exit Enter Request Select 1 from the configure menu to allow the admin user to add and delete users change passwords and change the outlet list The following menu appears if the unit has been re...

Page 14: ...er NOTE If you delete the user in the first position the ATS will display the following You are deleting the current admin user The next user will become the admin user do you want to continue Y N IMPORTANT The unit must have had a power cycle or unit reset command performed recently prior to deleting the user in the first position This action will prevent the unit from having No Admin user assign...

Page 15: ...let number s Select 3 to add all outlets to user access The unit will display Y for all outlets Select 4 to remove all outlets from a user The unit will display Y for all outlets Select 2 from the Configure Menu allows the admin user to change the names of the outlets Select this option and the unit displays all of the outlet names Default name is Outlet 1 Outlet number of outlets on unit Enter Re...

Page 16: ...t voltage switching points The processor uses a 6 cycle window to determine if the voltage is greater than zero but less than the trip threshold This should only be set after the ATSSET command has been performed This value can be tweaked according to loading It is recommended that the default values be maintained Enter Request 7 Disable switch back to primary Y N n Current delay switch back to pr...

Page 17: ...econdary source time is 3 Seconds Change delay switch to secondary time Y N Y Enter seconds 1 255 Enter Request 8 Disable delay switch to secondary Y N Y Enter Request Type N and press Enter The unit will display the current switch time and ask if you want to change the time Type N and press Enter and you will be sent back to the config menu Type Y and press Enter You will be asked to enter a time...

Page 18: ...r The unit will display Y N option Type Y and press Enter to disable the Over Current Buzzer Type N and press Enter to maintain current alarm state 1 Power loss buzzer alarm Off Default off 2 Over current buzzer alarm On Default On Enter Request 2 Press Enter The unit will display Y N option Type Y and press Enter to disable the Over Current Buzzer Type N and press Enter to enable the buzzer If th...

Page 19: ...C3 202 4 Volts Circuit C4 202 1 Volts Circuit C5 204 5 Volts Circuit C6 205 8 Volts Total kW h 0 Circuit Average Volt Group Power Amps Circuit M1 0 Watts 4 VA Circuit M2 0 Watts 4 VA Circuit M3 0 Watts 4 VA Circuit M4 0 Watts 4 VA Circuit M5 0 Watts 4 VA Circuit M6 0 Watts 4 VA Int Temp 95 9 F Ext 1 72 1 F 31 5 RH Ext 2 70 9 F Note Units with probes connected to external sensor ports will be displ...

Page 20: ...m field length is 32 or 16 for older unit Unit ID ATS18 Type source n n 1 or 2 at the ATS prompt This will change the input to the source selected and make it the primary input Type RIPSET at the outlet screen prompt to set the unit voltage The preset values are listed below The menu displays the current operating voltage and then asks the operator to choose the new operating voltage If no change ...

Page 21: ...ent Sensor threshold Firemware Config Download 11 Upload FTP firmware upload and download unit configuration Exit X CR Enter Request NOTE The following message Configuration mode in use signifies a user in the other port is in the Configuration menu Installed Modules 01 Attention Character is Disconnect Time Guard is Disabled Port ID Echo is Disabled Module Name is Universal RPC Network Connectivi...

Page 22: ... through the phone line via a modem The default settings are 9600bps 8 data bits no parity one stop bit RTS and DTR High IMPORTANT Communications with the terminal computer connected to the port will be lost until the serial port configuration of the terminal computer matches the unit s serial port Port Device Device Baud Word Stop Parity Handshake LineDrive Type Name Rate Size Bits DTR RTS 1 RS23...

Page 23: ...y it is very likely that these values could be transmitted as data and the transmission would fail Hardware Handshaking This style uses actual hardware lines Like the TX and Rx lines the RTS CTS and DTR DSR lines work together When a receiver is ready for data it will assert the RTS Request to Send line This is then read by the sender at the CTS Clear to Send input indicating it is clear to send t...

Page 24: ...sed for stop bits the greater the lenience in synchronizing the different clocks but the slower the data transmission rate Parity is a simple form of error checking used in serial communication For even and odd parity the serial port will set the parity bit the last bit after the data bits to a value to ensure that the transmission has an even or odd number of logic high bits For example if the da...

Page 25: ...etwork main menu Select 4 from the Network Configuration Menu sets the attention character The unit displays the following The Default is a semi colon Attention Character is Enter Attention Character Select 5 from the Network Configuration Menu ensures reliable binary data transmission by providing a one second Timeguard after the unit receives the attention character If more data is received with...

Page 26: ...sable prompt Press Enter to keep same setting Login prompt for serial is Disabled Enable Y N CR for no change If the login has been enabled you will get a prompt similar to the following The default user and password is root and baytech all lower case Universal RPC login root Password Select 2 from the Login setup Menu to allow the administrator to add delete users and change their passwords for m...

Page 27: ...1 Exit X Enter Request 1 Select 1 to change a user s password The unit displays the following menu User name root Enter old password CR if none If the user does not have a password the RPC will respond for a new password and a confirmation to re enter the new password Enter new password 31 characters Confirm by re entering new password Password change successful Select D Delete user The unit re di...

Page 28: ...et sets the shared radius secret A secret can be up to 16 characters and must be exactly the same as the secret stored on the server Select 5 Enable URPC usernames as backup enables URPC usernames as backup login allows an unsecured access until the RADIUS server becomes available Select 6 Radius Login Timeout sets the amount of time the unit will wait for a response from the radius server after s...

Page 29: ...6 Enable Disable encryption TACACS login Timeout 7 Sets Time units waits for response TACACS Server Port 8 Assign secure TCP port URPC Privilege Level Enable 9 Enable Disable TACACS privilege URPC Privilege Level 10 Set Privilege Level 1 15 Exit X CR Select 4 from the Login Setup Menu displays the TACACS Configuration menu Setting up TACACS To enable TACACS for logins do the following Enable TACAC...

Page 30: ...el Enable enables the unit to send a privilege level to the TACACS server Default is Disabled Select 10 URPC Privilege Level assigns privilege levels 1 is the minimum user privilege and 15 is the root admin privilege level Default is 15 Example of operation Privilege Level enabled set to 10 In tacacs conf file on daemon user1 is configured for exec priv lvl 9 user2 is configured for exec priv lvl ...

Page 31: ...tion process IP Filter allows or blocks specific IP Addresses SNMP provides a message format for communication between a computer and your devices and Web Server Configuration allows web access and sets up options for each Network setup Ethernet Address 00 C0 48 00 01 FD IP Address 70 150 140 89 Subnet Mask 255 255 255 224 Default Gateway 70 150 140 65 Connection Inactivity Timeout mins Disabled C...

Page 32: ...it is entered correctly Default Subnet Mask is 0 0 0 0 Select 3 to change the Gateway address Failure to enter the address in the decimal form causes the unit to display the following until it is entered correctly Default Gateway address is 0 0 0 0 Enter Gateway address in dotted decimal form Select 3 from Network Port Configuration Menu to set the amount of time the unit will wait before disconne...

Page 33: ... setting will logout all SSH and Telnet sessions Break Length is msec 350 Enter break length in milliseconds 10000 0 to disable Select 6 from Network Port Configuration Menu to enable or disable the DHCP feature Dynamic Host Configuration Protocol DHCP is a communications protocol that lets network administrators manage centrally and automate the assignment of Internet Protocol IP addresses in an ...

Page 34: ...ption to be available IP Filtering is ENABLED Enable Y N y Select E Enable IP Filtering to enable or disable the filtering function Filter added as Rule 1 Selecting either DROP or ACCEPT the packets and the RPC will assign filter the next rule number Please enter a single ip address filter or an ip address block in ip blockmask notation 70 150 140 95 Select a target option for this filter DROP the...

Page 35: ...e to work with your SNMP program Information provided is for the SNMP Agent only Baytech Support will assist with the Agent part only For SNMP Manger assistance refer to the vender manual or contact the vender of the SNMP software you are using NOTE There are a number of shareware MIB Browsers that can be downloaded from the internet to make changes and receive traps for a quick verification test ...

Page 36: ...P is ENABLED Enable Y N Select 8 SNMPv3 only Enable option if you have SNMPv3 software only the newer firmware will have this option Default is Disabled Caution The user password has to be 8 31 characters including the root user The client software will need the same password Select 9 SNMP Authentication Traps Enabled option to enable a SNMP trap to be sent if an authentication attempt failed the ...

Page 37: ... Login Activity Timeout 4 Exit X NOTE For this feature to operate the network port must have an IP Address assigned Type the unit s IP Address on a web browser to get the unit web page i e http 70 150 140 95 NOTE The web page is a quick test to see if SNMP protocol is working in the unit if SNMP has been enabled IMPORTANCE Currently all users who access the unit through the web page have administr...

Page 38: ...low current Enter the Selection Sel Number and press Enter Type a value in tenths of a volt i e 100 10 0 amps Sel M P Identifier Low Curr 1 2 1 MMP10 0 Enter threshold value in tenths of unit measurement degrees etc Enter voltage threshold value in tenths of a volt Enter low current threshold value in tenths of an amp NOTE M P Module number and Port number Identifier this unit s model number Tmp L...

Page 39: ...r threshold value in tenths of unit measurement degrees etc Select 1 to change the limits of individual probes Second line identifies the probe name and type Option 1 and 3 sets the temperature levels to the tenth of a degree Option 2 and 4 enable the SNMP traps to be sent if the corresponding threshold had been exceeded Select 2 to set parameters for the different probe types This feature is usef...

Page 40: ...ename Group 4 Modify Outlets in a Group 5 Delete All Outlet Groups 6 Enter Request 1 Select 6 from the RPC Management Menu allows user to combine outlets from different modules and ports One SNMP command is used to turn off on or reboot the group Select 1 to list any outlet groups Select 2 to add a new outlet group Each outlet is represented by Mod Port Outlet i e Mod 2 dot port dot outlet number ...

Page 41: ...e selected group and prompts for a new name Select 5 to modify outlets in a group select the number of the group to be modified The unit displays the selected group and prompts for new group of outlets Select 6 to delete all groups Note There will be no confirmation the groups have been deleted Select List Outlet Groups to verify all outlet groups were deleted Current temperature reported in degre...

Page 42: ...bled Enabling this feature will allow access and management of a BayTech Remote Power Device through the console EIA 232 port via telnet ssh SNMP http In RPC Cascade Mode normal console port terminal service will operate only when the network cable is disconnected When Cascade Mode is changed URPC module will RESET upon acceptance of configuration changes at which time cascade device should be con...

Page 43: ... 3 MOD 1 Outlet 1 18 3 MOD 1 Outlet 2 19 3 MOD 1 Outlet 3 20 3 MOD 1 Outlet 4 21 3 MOD 2 Outlet 1 22 3 MOD 2 Outlet 2 23 3 MOD 2 Outlet 3 24 3 MOD 2 Outlet 4 25 3 MOD 3 Outlet 1 26 3 MOD 3 Outlet 2 26 3 MOD 3 Outlet 3 28 3 MOD 3 Outlet 4 29 3 MOD 4 Outlet 1 30 3 MOD 4 Outlet 2 31 3 MOD 4 Outlet 3 32 3 MOD 4 Outlet 4 CMD Option O NOT Zero but the Letter O connects the outlet controls of both units ...

Page 44: ...ircuit Input List for device 1 MMP27 Inp PF Threshold Pwr Threshold W 1 0 50 The unit displays the number of Inputs on the unit Select an Input number to change the values for Power Factor PF Threshold and Power Threshold Input Threshold Menu Device 1 Input 1 Power Factor Threshold 0 Power Threshold 50 Power VA Power Factor Threshold 1 Minumum Power Threshold 2 Enter Request 1 Unit displays the In...

Page 45: ...e will generate an SNMP trap if enabled and power is above minimum power threshold A value of 0 disables threshold Enter threshold value NOTE The Power Factor Threshold SNMP alarm is sent only if both respective values drop below the Power Factor Threshold and Power Threshold at the same time Unit displays the Breaker Circuit Threshold Menu with current values Select 2 to change the Minimum Power ...

Page 46: ...wer Threshold 2 Enter Request Power VA ratio threshold as a percent between 0 and 100 inclusive Power factors below this value will generate an SNMP trap if enabled and power is above minimum power threshold A value of 0 disables threshold Enter threshold value Unit displays the Outlet Circuit Threshold Menu with Device Outlet number and current values Select 1 to change the Power Factor Threshold...

Page 47: ...r is below threshold Value will be applied to all circuits and outlets MMX units Enter threshold value Setting all Power VA Efficiency Thresholds to 80 Power Factor Threshold Menu Parameters to control generation of SNMP traps based on circuit Power VA power factor and minimum power level Sel M P Identifier Cks Outs 1 2 1 MMP 27 6 24 2 All Circuits Outlets Power Factor Threshold 3 All Circuits Out...

Page 48: ... create secure web connections The unit is shipped with a default SSL certificate This certificate should be replaced with one that better suits the user s environment The file format is checked after download to insure that the certificate is valid Enabling this will allow the SSL Certificate to be updated via ftp Enable SSL Certificate Upload Y N The unit will display the following IMPORTANT If ...

Page 49: ...om a computer to the power unit The unit will display the following IMPORTANT If you type Y the unit displays the following below To stop this function power cycle the unit to close the Configuration File Upload Enabling this will allow the system configuration to be updated via ftp THE UNIT WILL RESET AFTER CONFIGURATION IS COMPLETE Enable Configuration File Upload Y N Waiting to receive configur...

Page 50: ... not responding follow the reset procedures to reset the module Enabling this will allow the system configuration file to be retrieved via ftp Enable Configuration File Retrieval Y N Select Get Current Configuration File and the unit will display A YES response and the unit will display the following var confupload file created and ready for ftp retrieval Waiting to send configuration file At this...

Page 51: ...owing type Y at the prompt The unit will wait for the ASCII file to be transfer via FTP Send file in ASCII file mode Waiting for RC firmware Upgrading RC firmware on RPC at module 2 port 1 Enable update of Relay Controller firmware via Console RS232 port Enabling will reset Ethernet Module when Configuration is exited Enable Firmware Upgrade Y N y Send RC firmware file using ASCII file transfer op...

Page 52: ...er is responsible for properly packaging the product and for shipping costs for returns The customer is liable for loss or damage to the product during shipping as well as any other fees or charges associated with transporting the product back to BayTech BayTech will pay return costs for delivery within the Continental United States All repair and return shipments must be approved by BayTech and m...

Page 53: ...vernight replacements are available for purchase but only at the time of product purchase The extended warranty cost will not exceed 7 per year of the product list price unless otherwise stated in the customer contract or approved by BayTech management Contact BayTech for further details on this BayTech offers Tech Support for the lifetime of the product A staff of Applications Engineers is on dut...

Page 54: ...roduct Before dismantling equipment or returning the unit for any reason always contact BayTech Attempting to repair a product without BayTech authorization may result in voiding the warranty Follow the instructions below for repackaging and shipping NOTE Power should be disconnected from the power source before servicing or dismantling 1 Contact BayTech to get a Return Authorization RA Number IMP...

Page 55: ...hat was requested has been added to the unit concerning when the alarm lights and buzzer sounds There is NO Silence the Alarm 1 If the Alarm LED is light solid and the buzzer sounds without pauses you have an Over Current condition a Solution clear the over current condition 2 If the Alarm LED is light intermittent and the buzzer sound intermittent on a cyclic rate of long beep long pause than bee...

Page 56: ...e wrap bag 1U Bracket part number M140R115 Attach brackets to the each of the unit s side panel with two screws Verify both brackets are facing the same direction on the unit once attached 2U Bracket part number M140R114 Attach brackets to the each of the unit s side panel with two screws Verify both brackets are facing the same direction on the unit once attached Attach brackets and unit to rack ...

Reviews: