Page
38
RPC Management
Menu 3: Network RPC Management
Temperature Alarm Threshold
Under Voltage Alarm Threshold
Over Voltage Alarm Threshold
Low Current Alarm Threshold
Select 1),
to change the alarm for Internal Temperature:
Enter the Selection (Sel) Number and press Enter. Type a
value in tenths of a degree,
i.e.500 = 50.0
⁰
C
Sel M/P Identifier Tmp Lvl
1 2/1 MMP10 500
Select 2),
to change the alarm for Low Voltage: Enter the
Selection (Sel) Number and press Enter. Type a value in
tenths of a volt,
i.e 900 = 90.0 volts.
Sel M/P Identifier Lo V Lvl
1 2/1 MMP10 900
Select 3),
to change the alarm for over voltage: Enter the
Selection (Sel) Number and press Enter. Type a value in
tenths of a volt,
i.e 1300 =130.0 volts.
Sel M/P Identifier Hi V Lvl
1 2/1 MMP10 1300
Select 4),
to change the alarm for low current: Enter the
Selection (Sel) Number and press Enter. Type a value in
tenths of a volt,
i.e 100 =10.0 amps
Sel M/P Identifier Low Curr
1 2/1 MMP10 0
Enter threshold value in tenths
of unit measurement
(degrees,%,etc.):
Enter voltage threshold value in
tenths of a volt:
Enter low current threshold value
in tenths of an amp:
NOTE:
M/P = Module number and Port number; Identifier = this unit’s model
number; Tmp Lvl = temperature level, Lo V Lvl = low voltage level, Hi V Lvl
= High voltage level, low Curr = Low Current.
Host-controlled RPC Feature Configuration
Temperature Alarm Threshold........1
Under Voltage Alarm Threshold......2
Over Voltage Alarm Threshold.......3
Low Current Alarm Threshold........4
Environmental Sensors..............5
Outlet Groups......................6
Temperature units (degrees C/F)....7
Cascade Mode.......................8
Power Factor Threshold.............9
Select 10, from the Network Configuration
Menu
, to establish SNMP outlet traps used by a
remote SNMP Manager by creating outlet
groups and alarm thresholds.
Enter voltage threshold value in
tenths of a volt: