Page
20
Identify Current User
Unit Identification
Setting Source Input Primary
SETUP
OPTIONS
RIPSET
Current User: root
Type
Whoami
at the prompt to determine the current user, the unit will display the
following:
To change the user, logout of the unit and log back in using the new user name.
Type
Unitid
at the prompt to determine the Unit ID, the unit will display the following:
To change the unit ID, Go to the Outlet Configuration menu and select “Change Unit
ID’ option. The maximum field length is 32 or 16 for older unit.
Unit ID: ATS18
Type source ‘n’, (n= 1 or 2) at the ATS> prompt. This will change the input to the
source selected and make it the primary input.
Type
RIPSET
at the outlet screen prompt to set the unit voltage. The preset values
are listed below:
The menu displays the current operating voltage and then asks
the operator to choose the new operating voltage. If no change
is required press “Enter”, otherwise select the appropriate
number. Type “
X
” to exit the RIPSET routine.
Current operating voltage is: 208.0 Volts
Enter operating voltage
1)...100 Volts
2)...110 Volts
3)...120 Volts
4)...200 Volts
5)...208 Volts
6)...220 Volts
7)...230 Volts
8)...240 Volts
X)...Exit
Enter(1-8,X):