Page
47
All Circuits/Outlets - Power Factor Threshold
All Circuits/Outlets - Power Threshold
This option allows user to set all circuits and outlets to the same Power Factor Threshold levels.
(MMX) refers to the metered-outlet modular- series.
Default Value = (0%)
Power/VA ratio threshold as a percent, between 0 and 100, inclusive.
Power factors below this value will generate an SNMP trap, if enabled and
power is
above
minimum power threshold. A value of 0 disables threshold.
Value will be applied to all circuits and outlets (MMX units).
Enter threshold value:
This option allows user to set all circuits and outlets to the same Power Threshold levels. (MMX) refers
to the metered-outlet modular series.
Default Value = (50w)
Minimum power required to generate an SNMP power factor
trap if power factor is below threshold.
Value will be applied to all circuits and outlets (MMX units).
Enter threshold value:
Setting all Power/VA Efficiency Thresholds to 80%
Power Factor Threshold Menu
Parameters to control generation of SNMP traps based on
circuit Power/VA power factor and minimum power level
Sel M/P Identifier Cks #Outs
1 2/1 MMP-27 6 24
2 All
Circuits
/Outlets - Power Factor Threshold
3 All Circuits/Outlets - Power Threshold
Enter Request :
The unit responds with
message stating the
Thresholds were set to
the new value and
displays the Menu.
Setting all minimum Power Threshold levels to 10 Watts
Power Factor Threshold Menu
Parameters to control generation of SNMP traps based on
circuit
Power
/VA power factor and minimum power level
Sel M/P Identifier Cks #Outs
1 2/1 MMP-27 6 24
2 All Circuits/Outlets - Power Factor Threshold
3 All Circuits/Outlets - Power Threshold
Enter Request :
The unit responds with
message stating the
Thresholds were set to
the new value and
displays the Menu.