Page
44
Power Factor Threshold Menu
Individual Units
Parameters to control generation of SNMP traps based on
circuit Power/VA power factor and minimum power level
Sel M/P Identifier Circuits Outlets
1 2/1 MMP27 2 27
2 All Circuits/Outlets - Power Factor Threshold
3 All Circuits/Outlets - Power Threshold
Enter Request :1
Input Power Factor Thresholds......1
Circuit Power Factor Thresholds....2
Outlet Power Factor Thresholds.....3
Enter Request :1
Select 1),
to display Input Power
Factor (PF)
Select 9), from the RPC Management Menu,
to display the unit’s power efficiency on the web
page and through SNMP. The user sets a minimum power level that will send an SNMP trap to the
SNMP Manager. The smaller the power factor, less than (1), more current is needed (wasted) to
do the same amount work
M/P
= Module port,
Identifier
= Unit Id,
Circuits
= number of circuits on unit.
Outlets
= number of unit outlets.
Select 1);
to display current Power
Factor (PF) and Power Threshold
settings for each individual unit
circuit.
Input List for device 1, MMP27
Inp PF Threshold (%) Pwr Threshold (W)
1 0 50
The unit displays the number of Inputs
on the unit. Select an Input number to
change the values for Power Factor
(PF) Threshold and Power Threshold.
Input Threshold Menu
Device 1, Input 1
Power Factor Threshold: 0, Power Threshold: 50
Power/VA Power Factor Threshold....1
Minumum Power Threshold............2
Enter Request :1
Unit displays the Input Threshold
Menu with Device number, Input
number and current values.
Power/VA ratio threshold as a percent, between 0 and 100,
inclusive. Power factors below this value will generate an
SNMP trap, if enabled and power is above minimum power
threshold. A value of 0 disables threshold.
Enter threshold value:
NOTE:
The Power Factor Threshold SNMP alarm is sent only if both respective values drop
below the Power Factor Threshold and Power Threshold at the same time.
Select 2),
to change the Minimum
Power Threshold level. Enter a per
cent value (%).
Factory Default is
(0%).
Minimum power required to generate an SNMP power factor
trap if power factor is below threshold.
Enter threshold value:
Select 1),
to change the Power Factor
Threshold level. Enter a per cent
value (%).
Factory Default is (0%).