4. Ensure the support meets the following specifications:
Specifications
Examples
Flat surface that can support the
weight of the outdoor unit and its ac
cessories
Concrete base,
Sill,
Concrete blocks,
No rigid connection to the building served to avoid the transmission of vibration
Sufficient above ground elevation
(100 to 500 mm) to keep it above
water
Base with a metal frame to allow condensates to be discharged correctly.
The width of the base must not exceed the width of the outdoor unit.
The condensates discharge must be regularly cleaned in order to prevent any block
ages
6.4.3
Choosing the location of a noise abatement screen
When the outdoor unit is too close to neighbours, a noise abatement
screen can be fitted to reduce noise pollution.
Fig.33
MW-C000373-1
Brrrrr....
Brrrrr....
Br
rrr
r...
.
Brrrrr....
1. Locate the noise abatement screen as close as possible to the source
of noise whilst allowing for the free circulation of air in the exchanger
on the outdoor unit and maintenance work.
2. Respect the minimum positioning distances of the outdoor unit from
the noise abatement screen.
6.4.4
Selecting the location of the outdoor unit in cold and
snowy regions
Wind and snow can significantly reduce the performance of the outdoor
unit, the location of the outdoor unit must meet the following conditions.
Fig.34
MW-6000252-2
1
2
3
/
4
1. Install the outdoor unit sufficiently high off the ground to allow
condensates to be discharged correctly.