Operating description
4
Heating only. When the DP120 differential is reached, domestic hot water production is triggered.
If there is not enough domestic hot water (e.g. if the domestic hot water does not heat up quickly
enough): reduce the trip differential (hysteresis) by modifying the value of the DP120 parameter. The
DHW tank will then heat up the water more quickly.
5
Domestic hot water production only.
9.5.3
Running the back-up in domestic hot water mode
Start-up conditions for the back-up
The start-up conditions for the back-up producing domestic hot water are
described in the following table.
Tab.72
Parameter
Setting
AP001
The function of the BL1 blocking input is not set to 4, 6 or 8
AP100
The function of the BL2 blocking input is not set to 4, 6 or 8
Operating description
The behaviour of the hydraulic or electrical back-up in domestic hot water
mode depends on the configuration of the DP051 parameter.
Tab.73 Behaviour of the hydraulic or electrical back-up
Value of the parameter
DP051
Operating description
0
The system gives priority to the heat pump during domestic hot water production.
Recourse to the hydraulic or electrical back-up is only taken if the DP090 time delay has elapsed in
domestic hot water mode, unless hybrid mode is activated. In that case, hybrid logic takes over.
1
Domestic hot water production mode gives priority to comfort by accelerating domestic hot water pro
duction by simultaneously using the heat pump and the hydraulic or electrical back-up.
In this mode, there is no maximum time for domestic hot water production as the use of the back-ups
helps to ensure domestic hot water comfort more quickly.
9.6
Reading out measured values
The measured values are available in the Information menu of the
different PCBs.
Certain parameters are displayed:
according to certain system configurations,
according to the options, circuits or sensors actually connected.
Tab.74 Choosing the menu
Counters
Selection
Measured values on circuit A
Choose menu EHC-04
Measured values on circuit B
Choose menu SCB04-B
Measured values connected to the
operation of the heat pump
Choose menu EHC-04
Tab.75 Values available (X) in the sub-menus EHC-04, SCB04-B
Parameter
Description
Unit
EHC-04
SCB04-B
AM002
"Silent mode" status
X
AM010
The current pump speed
%
X
9 Settings
7706696 - v04 - 11102018
AWHP-2 PBS-i
89