Parameter
Description
Factory setting
DP150
Domestic hot water thermostat function.
Setting:
0: one sensor in use
1: Thermostat in use
0
DP160
Anti-legionella set point temperature.
Setting: 60 to 90 °C
65 °C
ADV
ADV advanced parameters
Tab.41 ADV advanced DHW parameters
Parameter
Description
Factory setting
ADV \ DP007
Position of three way valve during standby
0 =CH position
1 =DHW position
0
ADV \ DP055
Impressed current anode present:
0: No
1: Yes
0
ADV \ DP090
Electrical back-up start-up time delay for domestic hot water.
Can be set from 0 to 120 min
90 min
ADV \ DP100
Electrical back-up shutdown time delay for domestic hot water.
Can be set from 0 to 120 min
2 min
ADV \ DP110
Electrical back-up second stage start-up time delay for domestic hot water.
Can be set from 0 to 255 min
5 min
ADV \ DP130
Domestic hot water set point offset.
Can be set from 0 to 20 °C
8
ADV \ DP213
Post run time of the DHW pump/3 way valve after DHW production
Can be set from 0 Min to 99 Min
3
ADV \ DP334
Backup type used for DHW production:
0: indoor module electrical back-ups
1: DHW tank electrical back-ups
2: Indoor module electrical back-ups in winter/DHW tank electrical back-ups
for cooling
0
9.1.4
Installer \ CIRCA1 \ CIRCB1 \ DWH1 \ CIRCC1 \
CIRCAUX1 menu
Depending on the installation configuration, only certain circuits are
available. The CIRCA1 \ CIRCB1 \ DWH1 \ CIRCC1 \ CIRCAUX1 circuits
are on the SCB-10 PCB.
Tab.42 Correspondence between the parameters and the circuits
CPxx0 parameters ending in 0 correspond to the CIRCA1 circuit
CPxx1 parameters ending in 1 correspond to the CIRCB1 circuit
CPxx2 parameters ending in 2 correspond to the DHW1 circuit
CPxx3 parameters ending in 3 correspond to the CIRCC1 circuit
CPxx4 parameters ending in 4 correspond to the CIRCAUX1 circuit