1. Go to the Installer menu.
2. Access the Installer menu: enter the code 0012 by pressing the
and keys.
3. Confirm access by pressing the
key.
4. Select EHC–05 by pressing the or key.
5. Confirm access by pressing the
key.
6. Configure the HP033 parameters according to the type of energy
meter installed. By default, the pulse weight is set to 1 Wh, the setting
range of the HP033 parameter goes from 0 (no metering) to 1000 Wh.
If the pulse weight is given in kWh, refer to the following table.
Tab.68 If the pulse weight is given in kWh
Any numbers other than those stated in the table will not work.
Number of pulses in kWh Values to be configured for the HP033
parameter
1
1000
2
500
4
250
5
200
8
125
10
100
20
50
25
40
40
25
50
20
100
10
125
8
200
5
250
4
500
2
1000
1
7. Configure the HP034 and HP035 parameters.
Tab.69
Situation
Configuration
If an electrical back-up
is fitted
Set the HP034 and HP035 parameters according to the configuration of the electrical back-up stages
output.
9.4.7
Configuring a hydraulic back-up
Configure the back-up boiler according to its control panel. Set the installer
parameters.
1. Switch the boiler control system to 24h/24 comfort mode.
2. Heating set point temperature = Domestic hot water set point
tempe 5°C.
See
Boiler installation manual.
9.4.8
Configuring a convection fan or underfloor cooling
This function is only available when the type of circuit selected is
underfloor heating or convection fan:
Circuit
Parameter
Value of the parameter
CIRCA0
CP020
2 or 5
CIRCA1
CP020
2 or 5
9 Settings
78
iHPI