Parameter
Description
Factory setting
SCB-10
BP015
Minimum duration of post-operation of the buffer tank pump
Can be set from 0 Min to 20 Min
4
BP019
Hysteresis of temperature which determines the stop of buffer tank storage
Can be set from -30 °C to 30 °C
0
Tab.47 EP : Entry Parameters = Input parameters
Parameter
Description
Factory setting
SCB-10
EP014
Smart Control Board function 10 Volt PWM input
0 Off
1 Temperature control
2 Power control
0
EP018
Status relay function
0 =No Action
1 =Alarm
2 =Alarm Inverted
3 = Compressor on
4 = Compressor off
5 =Reserved
6 =Reserved
7 =Service request
8 = Heat pump into heating mode
9 = Heat pump in domestic hot water mode
10 =CH pump on
11 =Locking or Blocking
11
EP030
Sets the minimum set point temperature for 0 - 10 volts for the Smart Control
Board
Can be set from 0 °C to 100 °C
0
EP031
Sets the maximum set point temperature for 0 - 10 volts for the Smart Control
Board
Can be set from 0.5 °C to 100 °C
100
EP032
Sets the minimum set point power for 0 - 10 volts for the Smart Control Board
Can be set from 0 % to 100 %
0
EP033
Sets the maximum set point power for 0 - 10 volts
Can be set from 5 % to 100 %
100
EP034
Minimum voltage for 0-10 V input corresponding to the minimum set point
Can be set from 0 V to 10 V
0.5
EP035
Maximum voltage for 0-10 V input corresponding to the maximum set point
Can be set from 0 V to 10 V
10
EP046
Sets the general configuration of the digital input
0 =Stop h DHW
1 =Stop heating
2 =Stop DHW
3 =Forced setpoint
4 =Buffer Tank input
0
EP056
Sets the logic level contact of the Smart Control Board digital input
0 =Open
1 =Closed
2 =Off
1
EP066
Requested flow setpoint when digital input is configured to forced heat
Can be set from 7 °C to 100 °C
80
EP076
Requested power setpoint when digital input is configured to forced heat
Can be set from 0 % to 100 %
100
9 Settings
7701563 - v02 - 22052018
iHPI