Parameter
Factory setting for each circuit
Description
CP690
CP691
CP692
CP693
CP694
CIRCA1: 0
CIRCB1: 0
DHW1: 0
CIRCC1: 0
CIRCAUX1: 0
Reversed Opentherm contact in cooling mode for heat demand per
zone
0 =No
1 =Yes
CP700
CP701
CP702
CP703
CP704
CIRCA1: 0
CIRCB1: 0
DHW1: 0
CIRCC1: 0
CIRCAUX1: 0
Offset for calorifier sensor per zone
Can be set from 0 °C to 30 °C
CP710
CP711
CP712
CP713
CP714
CIRCA1: 20
CIRCB1: 20
DHW1: 20
CIRCC1: 20
CIRCAUX1: 20
Increase Primary Temperature setpoint for heating DHW calorifier of
the zone
Can be set from 0 °C to 40 °C
CP720
CP721
CP722
CP723
CP724
CIRCA1: 20
CIRCB1: 20
DHW1: 20
CIRCC1: 20
CIRCAUX1: 20
Increase Primary Temperature setpoint for process heat calorifier of
the zone
Can be set from 0 °C to 40 °C
CP750
CP751
CP752
CP753
CP754
CIRCA1: 0
CIRCB1: 0
DHW1: not used
CIRCC1: 0
CIRCAUX1: 0
Maximal Zone Preheat time
Can be set from 0 Min to 240 Min
CP760
CP761
CP762
CP763
CP764
CIRCA1: 0
CIRCB1: 0
DHW1: 1
CIRCC1: 0
CIRCAUX1: 0
The calorifier of the zone is equipped with a Titan Active System
anode
0 =No
1 =Yes
CP780
CP781
CP782
CP783
CP784
CIRCA1: 0
CIRCB1: 0
DHW1: not used
CIRCC1: 0
CIRCAUX1: 0
Selection of the control strategy for the zone
0 =Extra Slow
1 =Slowest
2 =Slower
3 =Normal
4 =Faster
5 =Fastest
ADV
ADV advanced parameters
Tab.44 Advanced parameters of the CIRCA1 \ CIRCB1 \ DWH1 \ CIRCC1 \ CIRCAUX1 heating circuits
Parameter
Factory setting for each circuit
Description
ADV \ CP290
ADV \ CP291
ADV \ CP292
ADV \ CP293
ADV \ CP294
CIRCA1: 0
CIRCB1: 0
DHW1: not used
CIRCC1: 0
CIRCAUX1: 8
Configuration of Zone Pump Output
0 =Zone output
1 =CH mode
2 =DHW mode
3 =Cooling mode
4 =Error report
5 =Burning
6 =Service flag
7 =System error
8 =DHW looping
9 =Primary pump
10 =Buffer pump
ADV \ CP330
ADV \ CP331
ADV \ CP332
ADV \ CP333
ADV \ CP334
CIRCA1: 60
CIRCB1: 60
DHW1: not used
CIRCC1: 60
CIRCAUX1: 60
The time needed by the valve to be fully opened
Can be set from 0 Sec to 240 Sec
9 Settings