Circuit
Parameter
Value of the parameter
CIRCB1
CP021
2 or 5
CIRCC1
CP023
2 or 5
CIRCAUX1
CP024
2 or 5
Important
The heating should be activated in order for cooling to function.
1. Go to the Installer menu.
2. Access the Installer menu by entering the code 0012 by pressing the
and keys.
3. Confirm access by pressing the
key.
4. Access the EHC–05 PCB parameters by pressing the or key.
5. Select the AP028 parameter corresponding to cooling by pressing the
or keys.
6. Confirm by pressing the
key.
7. Select value 1 by pressing the key to activate the cooling function.
8. Confirm by pressing the
key.
9. Go back to the main display by pressing
h
.
10. Program the desired cooling hours in the menu, circuit A or B, TP.C
sub-menu.
11. Go back to the main display by pressing
h
.
12. If necessary, force cooling or configure cooling temperatures in the
User menu, circuits A and B:
Tab.70
Parameter
Description
AP015
Cooling is forced, regardless of the outdoor temperature
AP016
Activating/deactivating heating: deactivating heating also deactivates cooling
CP270 on the CIRCA0 circuit
CP270 on the CIRCA1 circuit
CP271 on the CIRCB1 circuit
CP273 on the CIRCC1 circuit
CP274 on the CIRCAUX1 circuit
Cooling set point for the flow temperature on the underfloor cooling circuit
CP280
CP280 on the CIRCA0 circuit
CP280 on the CIRCA1 circuit
CP281 on the CIRCB1 circuit
CP283 on the CIRCC1 circuit
CP284 on the CIRCAUX1 circuit
Cooling set point for the flow temperature on the convection fan circuit
13. Check the setting for the CP690 parameters according to the
thermostat or room sensor used.
9.4.9
Screed drying with the aid of the heat pump
The screed drying program reduces the drying time of a freshly poured
screed floor.
The settings for these temperatures must follow the screed layer's
recommendations.
Activating this function via the CP470, CP471, CP473 or CP474
parameter (setting other than 0) forces the permanent display of the
screed drying function and deactivates all the other regulator functions.
When the screed drying function is active on one circuit, all other circuits
and the domestic hot water circuit continue to run.
Fig.89
MW
-4
0
0
0
1
9
7
-2
Fig.90
MW-6000366-3
9 Settings
7701563 - v02 - 22052018
iHPI