Product name
iHPI
AWHP 22 TR–2
iHPI
AWHP 27 TR-2
Stand-by
P
SB
kW
0.016
0.023
Crankcase heater mode
P
CK
kW
0.055
0.055
Supplementary heater
Rated heat output
Psup
kW
0.0
0.0
Type of energy input
Electricity
Electricity
Other specifications
Capacity control
Variable
Variable
Sound power level, indoors - outdoors
L
WA
dB
43 _ 77
43 _ 77
Annual energy consumption under average conditions
Q
HE
kWh 7681
9993
Annual energy consumption under colder conditions
Q
HE
kWh 10578
13164
Annual energy consumption under warmer conditions
Q
HE
kWh 10025
11541
Rated air flow rate, outdoors for air-to-water heat pumps
—
m
3
/h 6000
6000
(1) The rated heat output
Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater
Psup is equal to the supplementary capacity for heating sup(Tj).
(2) If
Cdh is not determined by measurement, the default degradation coefficient is Cdh = 0.9.
See
The back cover for contact details.
3.2.4
Sensor specifications
Outside sensor specifications
Tab.9
Outside sensor
Temperature
°C
-20
-16
-12
-8
-4
0
4
8
12
16
20
24
Resistance
Ohm
2392 2088
1811
1562 1342 1149
984
842
720
616
528
454
Flow sensor specifications
Tab.10 Flow sensor
Temperature in
°C
0
10
20
25
30
40
50
60
70
80
90
Resistance in Ω
32014
19691
12474
10000
8080
5372
3661
2535
1794
1290
941
PT1000 sensor specifications
Tab.11 PT1000 condenser flow and return sensors
Temperature
°C
-10
0
10
20
30
40
50
60
70
80
90
100
Resistance
Ohm
961
1000
1039
1077 1117 1155 1194
1232 1271 1309 1347 1385
3 Technical specifications
14
iHPI
7701563 - v02 - 22052018