Parameter
Description
Factory setting
EHC–05
Factory setting
SCB-10
AP058
Warning message indicating that pressure is low
Can be set from 0 bar to 2 bar
0.8
not available
AP069
Maximum time the top-up filling may last
Can be set from 0 Min to 65535 Min
5
not available
AP070
The operational water pressure the device should be working on
Can be set from 0 bar to 2.5 bar
2
not available
AP071
Maximum time that is needed to fill the complete installation
Can be set from 0 Sec to 3600 Sec
1000
not available
AP073
Outdoor temperature: upper limit for heating
Can be set from 15 °C to 30.5 °C
not available
22
AP075
Outdoor temperature neutral band between heating and cooling. The
generator is stopped.
Can be set from 0 to 10 °C
not available
4
AP079
Inertia of the building used for heat up speed
Can be set from 0 to 10
0 = 10 hours for a building with low thermal inertia,
= 22 hours for a building with normal thermal inertia,
10 = 50 hours for a building with high thermal inertia.
Modification of the factory setting is only useful in exceptional cases.
not available
3
AP080
Outside temperature below which the antifreeze protection is
activated:
can be set from -29 to 20 °C
set to -30 °C = function deactivated
not available
3
AP082
Enable daylight saving for the system to save energy during winter
0 to Off
1 to On
1
not available
AP083
Enable the master functionality of this device on the S-Bus for
system control
0 =No
1 =Yes
not available
0
AP091
Outdoor sensor type
0 =Auto
not available
0
Tab.46 BP : Buffer Parameters = Buffer tank parameters
Parameter
Description
Factory setting
SCB-10
BP001
Type of Buffer Tank
0 =Disabled
1 =One sensor
2 =Two sensors
3 =Three sensors
0
BP002
Heating Cooling Control strategy used with buffer tank
0 =Fixed setpoint
1 =Calculated setpoint
2 =Dedicated slope
0
BP003
Temperature setpoint for Buffer tank in heating mode
Can be set from 5 °C to 100 °C
70
BP004
Temperature setpoint for Buffer tank in cooling mode
Can be set from 5 °C 25 °C
18
BP005
Buffer Tank Slope
Can be set from 0 4
1.5
BP013
Offset to add to the calculate Setpoint of the Buffer Tank
Can be set from 0 °C 20 °C
5
BP014
Hysteresis of temperature which determines the start of Buffer Tank storage
Can be set from 1 °C to 20 °C
6