2. Put the 2 plugs in place, delivered with the sensor.
Plugs diameter 4 mm/drill diameter 6 mm
3. Secure the sensor using the screws provided (diameter 4 mm).
4. Connect the cable to the outdoor temperature sensor.
Recommended positions
Place the outside sensor in a position that covers the following
characteristics:
On a façade of the area to be heated, on the north if possible.
Half way up the wall of the area to be heated.
Under the influence of changes in the weather.
Protected from direct sunlight.
Easy to access.
Fig.43
MW-8800N001-3
2
1
2
1
1
2
H
1/2 H (min. 2,5 m)
1/2 H (min. 2,5 m)
1/2 Z
H
Z
1 Optimum location
2 Possible position
H Inhabited height controlled by the sensor
Z Inhabited area controlled by the sensor
Positions to be avoided
Avoid placing the outside sensor in a position with the following
characteristics:
Masked by part of the building (balcony, roof, etc.).
Close to a disruptive heat source (sun, chimney, ventilation grid, etc.).
Fig.44
MW-3000014-2
Fig.42
MW-8800N003-6
2
3
4
6 Installation