Recommissioning
Instruction handbook
b maXX
BM3000, BM3200, BM3300
Document no. 5.11018.11
Baumüller Nürnberg GmbH
202
12.6
12.6 Recommissioning
Execute commissioning as with a new device, see
.
CAUTION!
Recommissioning without forming of the capacitors.
From six months storage period on, the capacitors are destroyed during commission-
ing, if they are not formed beforehand
m
Reform the DC link capacitors:
n
by supplying the device ready-to-operate for at least one hour with
supply voltage
n
but do not transmit a pulse enable during this time.
m
Consider, that it is imperative, to connect the accordingly prescribed line commu-
tating reactor for this forming procedure. Devices, where no line commutating re-
actor is necessary can directly be supplied with power supply voltage.