Optional safety function STO of BM3300
Instruction handbook
b maXX
BM3000, BM3200, BM3300
Document no. 5.11018.11
Baumüller Nürnberg GmbH
154
8.5
8.5.4
Timing
24V STOA
24V STOB
STO
VWDWH
"S01"
STO
VWDWH
"S02"
Td
Td
Td2
Td2
Td
Td
Td
Td2
QRW
STO
QRW
STO
QRW
STO
QRW
STO
QRW
STO
STO
STO
STO
STO
STO
Figure 62:
Timing STO function
T
d
: < 40 ms
T
d2
: max. 30 ms
n
the controller is enabled after 40 ms, when both voltages are activated
n
the controller is disabled after max. 30 ms, when one voltage deactivated
8.5.5
Supply with separate power supplies
GND
GND
+24 V
+24 V
Figure 63:
Supply with separate power supplies