Accessories and Spare Parts
Instruction handbook
b maXX
BM3000, BM3200, BM3300
Document no. 5.11018.11
195
11
11.3.3 Mains filter for 1-phase devices BM3XXX-XEXX
m
Selection of the correct mains filter for 1-phase devices
In dependency of the application install a mains filter from the following table:
m
Electrical data mains filter for 1-phase devices
LGF mains filter
FFU 1X12B-SB02
Max. supply voltage
1 x 250 V
AC
, 120 Hz
Rated current (at T
B
=
40 °C)
12 A
Peak current (at T
B
= 40 °C)
1.5 x I
N
for < 1 min per hour
Max. test voltage
for 2 s at 25 °C
phase / phase: 1.7 kV
DC
phase / housing:
2.7 kV
DC
Maximum conductor cross
sections
4 mm
2
fine wire
6 mm
2
rigid wire
Leakage power (typical)
9 W
Ground current
typical 7 mA, at 250 V/50 Hz
Type of protection
IP 20
Weight
0.6 kg
I
Bem AC
1)
Type
Part No.
Use with devices
12 A
LGF mains filter
FFU 1X12B-SB02
463472
BM32XX-X
E
XX
BM33XX-X
E
XX
DANGER!
Risk of fatal injury from high leakage current!
Therefore:
m
Cross-section of the PE conductor see
PE connections BM3200, BM3300 rear
on page 145 (EN 61800-5-1, chapter 4.3.5.5.2).
NOTE!
The rated current of the used filters must be greater or the same RMS value of the
actual power supply current (actual power supply current = RMS value of the power
supply current during the total cycle time of the drive). At short-time operation (S3)
the RMS value is calculated as follows:
I
eff
1
T
---
i
2
0
T
dt
=