Fuses
Instruction handbook
b maXX
BM3000, BM3200, BM3300
Document no. 5.11018.11
Baumüller Nürnberg GmbH
192
11.2
11.2.3 Cable protection and device protection
There are two possibilities to protect the cable and the device:
m
Cable protection fuses and semiconductor fuses, which are connected in series
m
Use all-range fuses with a tripping characteristic gR or gS (DIN VDE 0636-201 / IEC
60269-2-1 / HD 630.2.1 54).
The suitable cable and device protection fuses must be dimensioned dependent on the
interface of the used power supply cable, the peak current and of the required I
2
t
off
in
In contrast to the fuses, the devices and cables can be protected with listed „Circuit break-
ers“ complying to UL (DIVQ).
Permitted are circuit breakers without a tripping delay, only. Circuit breakers with only a
thermal tripping characteristic are not tested and therefore not permitted. It must be con-
sidered that the installation is protected against fire but not against destruction.
Dimension the circuit breaker dependent on the interface of the used power supply cable
as well as from the rated and the peak current of the devices.
BM3002
Producer
Device protection
Device protection and cable protection
Siemens
3NE8 003-1: 35A/690V, NH00, gR
3NE8 702-1: 40A/690V, NH000 gR
Producer
Device protection
Device protection and cable protection
SIBA
60 033 05 16A (10 x 38 mm) aR
20 477 34 16A (NH000) gRL gS
20 209 34 16A (NH00) gRL gS
50 124 34 16A (14 x 51 mm) gRL gS
Bussmann
FWP-20A14F 20A 700V 14x51mm aR
170M1560D 20A 690V NH000 gR
DFJ-15 (21 x 57 mm) Class J
Mersen
(former Ferraz)
NH000GS69V32PV Ref:X322043C
(NH000) 32A 690V gS
FR10GR69V20 Ref: E1014580
(10 x 38 mm) 20A 690V gR
FR22GC69V25 Ref: B220916
(22 x 58 mm) 25A 690V gRC
HSJ15 (21 x 57 mm) Class J
Siemens
3NC1415: 15A/690V, (14 x 51 mm) aR
3NC1016: 16A/600V, (10 x 38 mm) aR
3NE1813-0: 16A/690V, NH000 gS
3NE8015-1: 25A/690V, NH00 gR