124
7.14
CANopen
®
Type code
BM3200, BM3300
with CANopen
®
:
BM3XXX-XXXX-XXXXX[-X]-
3
XXXX[-S0X]-XX[-XX][-EXX][-#XX]
X3
X4
CANopen
®
IN
CANopen
®
OUT
Memory
4 kByte DP-RAM, 256 kByte RAM,
1 MByte Flash-EPROM
Number of bus connections
2, no slot rules
Bus connection
2 connectors RJ45, 8-pin
Baud rates
20/125/250/500/1000 kBit/s
Address range
7 Bit; address 1 to address 127
Address setting
DIP-switch
Short-circuit proof RJ45-connection
Yes
Isolation
Optocoupler, DC/DC-converter
1
: CAN_H
2
: CAN_L
3
: GND
4
: reserved
5
: reserved
6
: GND
7
: reserved
8
: reserved
X3
X4