WARNING: Do not spray slurry on insulators and poles !
Safety distance Z in m, measured on the ground
Type and operation mode
of the sprinkler
With rubber wheels or directed by hand
With metal or synthetic pipes
With skids or stationary/fixed
With metal cart and metal pipes
Nozzle diameter in mm or. Flow in m
3
/h
26 mm
≙
50 m
3
/h 36
mm
≙
100 m
3
/h 26
mm
≙
50 m
3
/h 36
mm
≙
100 m
3
/h
Jet
type
Spray Full Spray
Full Spray Fulll Spray Full
Up to 1.000 V
H = 1 m
ZR
1 5 1 5 1 5 1 5
ZG
1 8 1 8 1 8 1 8
Up to 30.000 V
H = 2,5 m
ZR
3 9 5 21 3 7 4 9
ZG
5 11 7 23 5 9 6 11
Up to 110.000 V
H = 3 m
ZR
3 12 5 24 3 9 4 15
ZG
5 14 7 26 5 11 6 17
Up to 220.000 V
H = 4 m
ZR
4 14 6 26 4 12 6 22
ZG
6 16 8 28 6 14 8 24
Up to 380.000 V
H = 5 m
ZR
5 16 7 26 5 14 6 22
ZG
7 18 9 28 7 16 8 24
The indicated safety distances in the above chart are valid for a nozzle diameter of 26 mm or 36 mm at an operating pressure of
5 bar.
For higher operating pressures the safety distances have to be increased by 2 m.
The safety distances are not valid
when normed jet pipes, like they are used by fire brigades, are being used.
When applying polluted water or slurry, note that a conductive layer can build up on the insulators.
Therefore do not spray on
the insulators.!
Flashovers and insulator damage can otherwise cause power failure.
If metal sprinkler pipes are laid parallel to a high voltage power line, this can lead, even without irrigating, to a perceptible
contact voltage because of the electric influence. Touching the pipes is not dangerous, but can be unpleasant and painful. This
is why it should be avoided to lay metal pipes parallel to high voltage lines or only over the shortest distances possible. When
using synthetic pipes, you will not encounter any of these problems.
NOTE ! DO NOT PUT PIPE LINE PIECES INTO A VERTICAL POSITION IN THE RANGE OF HIGH VOLTAGE LINES !