3.9 Genset Installation Recommendations
Users must choose the genset installation location very carefully in order to not disturb anyone
and not to cause noise pollution. If the location is not appropriate, enclosure has to be insu-
lated for noise reduction. Also, the correct type of exhaust silencer must be used if necessary.
The genset room should be well ventilated. The foundation of the unit should be solid and
conform to local code. After compacting hard soil, the minimum precast concrete structure
foundation of 200mm thick should be built on this foundation.
When installed, the shock absorber is evenly placed under the two channel steel of the
common chassis of the unit, leveling with the flat pad, and its levelness is measured with
the level gauge. Keep the unit level; In addition, the packaging base is not allowed to be
used as the basis for starting up operation.
When the user is building the genset room, the steel I-beam for lifting should be embed-
ded in the roof above the unit for later maintenance.
The inner diameter of the exhaust pipe should not be less than 140mm, the bending pipe
should not be more than 3, and the bending Angle should be greater than 90 degrees.
There should be sufficient maintenance and inspection space around the unit. There
should be at least 1.5m space around the unit.
The machine room should be equipped with fire extinguishers and other fire tools
Figure 3.9-Genset installation
Summary of Contents for 12M26 Series
Page 1: ...1 1003195965 ...
Page 2: ...2 Operation and Maintenance Manual for PowerKit M26 Series Diesel Engine GDMB26V1901 ...
Page 31: ...O M Manual for PowerKit M26 Series Diesel Engine 31 12M26MP Figure 3 2B 12M26 Mounting ...
Page 78: ...O M Manual for PowerKit M26 Series Diesel Engine 78 6 6 Engine Maintenance Log ...
Page 79: ...O M Manual for PowerKit M26 Series Diesel Engine 79 ...