Programming guidelines
ACOPOSinverter P84 User's Manual 2.10
121
2.8.3 Independence of the parameter values
To reduce the risk of errors, the configuration of certain parameters changes the setting range of other parameters.
This
can result in a change in a default setting or a previously selected value.
1
[Current Limiting]
see "Setting parameters (SFr - CL2)" on page 144
set to 1.6 in or left on default
value 1.5 in
2
[Frequency]
(SFr)
see "Setting parameters (SFr - CL2)" on page 144
is set to 1 kHz (and confirmed with
"ENT") limited
[Current limiting]
(CLI)
to 1.36 in
3 If
[Frequency]
(SFr)
is increased to 4 kHz,
[Current limiting]
(CLI)
is no longer limited, but remains at
1.36 In. If you need 1.6 In, you must reset
[Current limiting]
(CLI)
.