Integrated safety functions
354
ACOPOSinverter P84 User's Manual 2.10
3.6 Technical data
3.6.1 Electrical data
The logical inputs and outputs of the inverter can be wired for the logic type 1 or logic type 2.
Logic type
Active state
1
Output drawing current (source)
Current flows to the input
2
Output emits current from the input
Power source (sink)
Safety functions are only used in sink mode; source mode is not compatible with the safety functions.
The signal inputs are protected against polarity reversal, while the outputs are protected against short circuits. Both
the inputs and the outputs are electrically isolated.
3.6.2 Capacity of the safety functions
3.6.2.1 The safety functions of the safety-relevant power frequency inverter PDS(SR)
If, for the achievement of the qualitative and quantitative security objectives of the end application, certain adjust-
ments must be made to ensure that the security functions can be used in a safe manner, the BDM-integrator is
responsible for these additional developments (e.g. management of the mechanical motor brake).
In addition, the output data generated when using the safety functions (standard relay activation, controlling the
brake logic relay, error codes, information on the display, etc.) do not comprise safety-related features.
Function
PWR (STO)
Standard
Configuration
PWR (STO) with safety relay
IEC 61800-5-2 /
IEC 61508 /
SIL 2
IEC 62061 (1)
SIL 2 CL
EN 954-1 (2)
Category 3
ISO 13849-1 (3)
Category 3
PL "d"
IEC 60204-1
Stop category 0
(1)
Since the standard IEC 62061 is an integration standard, the global safety function (according to SIL 2 ACOPOSinverter P84 - the charts process system
SF - Case 1
see "Process system SF - Case 1" on page 360
and process system SF - Case 2
see "Process system SF - Case 2" on page 362
) and the
individual components of the safety function (according to SIL 2 CL for ACOPOSinverter P84) are differentiated between.
(2)
See table 6 in the IEC 62061 (2005) standard.
(3)
See table 4 in the EN 13849-1 (2008) standard.
3.6.2.2 Processor application
Function
PWR (STO)
Standard
Configuration
PWR (STO)
IEC 61800-5-2 /
IEC 61508 /
SIL 2
IEC 62061 (1)
SIL 2 CL
(1)
Since the standard IEC 62061 is an integration standard, the global safety function (according to SIL 2 ACOPOSinverter P84 - the charts process system
SF - Case 1
see "Process system SF - Case 1" on page 360
and process system SF - Case 2
see "Process system SF - Case 2" on page 362
) and the
individual components of the safety function (according to SIL 2 CL for ACOPOSinverter P84) are differentiated between.
3.6.2.3 Input signals of the safety functions
Input signals of the safety functions
Unit
Value for
LI3 to LI6
Value for STO
Logic 0 (Ulow)
V
<5
<2
Logic 1 (Uhigh)
V
>11
>17
Impedance (24 V)
kΩ
3.5
1.5
Debounce time
ms
<1
<1
Response time of the safety function
ms
<10
<10
Summary of Contents for 8I84T200037.01P-1
Page 2: ......
Page 391: ...Accessories ACOPOSinverter P84 User s Manual 2 10 391 4 7 2 Installation 8I0XF084 020 1...
Page 392: ...Accessories 392 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 030 1...
Page 393: ...Accessories ACOPOSinverter P84 User s Manual 2 10 393 8I0XF084 040 1...
Page 394: ...Accessories 394 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 050 1...
Page 395: ...Accessories ACOPOSinverter P84 User s Manual 2 10 395 8I0XF084 0x0 1...
Page 400: ...Accessories 400 ACOPOSinverter P84 User s Manual 2 10...