Programming guidelines
ACOPOSinverter P84 User's Manual 2.10
173
[AI1 CONFIGURATION] (AI1-)
Code
Name/Description
Setting range
Factory settings
AI1-
[AI1 CONFIGURATION]
AI1A
[AI1 assignment]
Read-only parameter, cannot be configured.
This parameter displays all functions assigned to the AI1 input. This allows compatibility problems to be checked, for example.
AI1t
[Type AI1]
[0-10V]
(10U)
10U
[0-10V]
(10U)
: Positive voltage input (negative values are interpreted as zero: the input is unidirectional)
n10U
[+/- volt]
(10U)
: Positive and negative voltage input (input is bi-directional).
UIL1
[AI1 min value]
0 to 10 V
0 V
UIH1
[AI1 max value]
0 to 10 V
10 V
AIF1
[AI1 filter]
0 to 10 s
0 s
Filter
AI1E
[AI1 Interm. point X]
0 to 100%
0%
Coordinate of the delinearization point at the input.
•
0% corresponds to
[min. value]
(UIL1)
.
•
100% corresponds to
[max. value]
(UIH1)
.
AI1S
[AI1 Interm. point Y]
0 to 100%
0%
Output delinearization point coordinate (frequency reference).
[AI2 configuration](AI2-)
Code
Name/Description
Setting range
Factory settings
AI2-
[AI2 CONFIGURATION]
AI2A
[AI2 assignment]
Read-only parameter, cannot be configured.
This parameter displays all functions assigned to the AI2 input. This allows compatibility problems to be checked, for example.
AI2t
[Type AI2]
[current]
(0 A)
10U
[voltage]
(10U)
: Voltage input
0 A
[current]
(0 A)
: Current input
CrL2
[AI2 min value]
0 to 20 mA
0 to 20 mA
Parameter accessible if
[Type AI2]
(AI2t)
=
[Current]
(0 A)
.
UIL2
[AI2 min value]
0 to 10 V
0 V
Parameter accessible if
[Type AI2]
(AI2t)
=
[Voltage]
(10U)
.
CrH2
[AI2 max value]
0 to 20 mA
20 mA
Parameter accessible if
[Type AI2]
(AI2t)
=
[Current]
(0 A)
.
UIH2
[AI2 max value]
0 to 10 V
10 V
Parameter accessible if
[Type AI2]
(AI2t)
=
[Voltage]
(10U)
.
AI2F
[AI2 filter]
0 to 10 s
0 s
Filter.
AI2L
[AI2 range]
[0 - 100%]
(POS)
POS
[0 - 100%]
(POS)
: Unidirectional input
nEG
[+/- 100%]
(nEG)
: Bidirectional input
Example: At an input of 0 to 10 V
•
0 V corresponds to the reference -100%.
•
5 V corresponds to the reference 0%.
•
10 V corresponds to the reference 100%.
AI2E
[AI2 Interm. point X]
0 to 100%
0%
Input delinearization point coordinate.
•
0% corresponds to
, when the range = 0 100%.
• 0% corresponds to when the range = -100% 100%
• 100% corresponds to
.
[Min value]
[Max value]
[Max value] [Min value]
+
2
AI2S
[AI2 Interm. point Y]
0 to 100%
0%
Output delinearization point coordinate (frequency reference).
Summary of Contents for 8I84T200037.01P-1
Page 2: ......
Page 391: ...Accessories ACOPOSinverter P84 User s Manual 2 10 391 4 7 2 Installation 8I0XF084 020 1...
Page 392: ...Accessories 392 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 030 1...
Page 393: ...Accessories ACOPOSinverter P84 User s Manual 2 10 393 8I0XF084 040 1...
Page 394: ...Accessories 394 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 050 1...
Page 395: ...Accessories ACOPOSinverter P84 User s Manual 2 10 395 8I0XF084 0x0 1...
Page 400: ...Accessories 400 ACOPOSinverter P84 User s Manual 2 10...