ACOPOSinverter P84 User's Manual 2.10
1.3.6.1 Derating curves
Declassification curves for the inverter current (In) based on temperature and switching frequency.
8I84T200037.01P-1 to 8I84T201500.01P-1 and 8I84T400075.01P-1 to 8I84T401850.01P-1
40°C Installation type B
40°C Installation type A
50°C Installation type B
50°C Installation type A
Clock frequency
I/In
60°C Installation types
A and B
8I84T402200.01P-1 and 8I84T403000.01P-1 (1)
Clock frequency
I/In
40°C Installation types
A and B
50°C Installation types
A and B
60°C Installation types
A and B
8I84T201850.01P-1 to 8I84T204500.01P-1 and 8I84T403700.01P-1 to 8I84T407500.01P-1 (1)
Clock frequency
I/In
40°C Installation types
A and B
60°C Installation types
A and B
50°C Installation types
A and B
At intermediate temperatures (e.g. 55°C), the values of the two curves must be interpolated.
(1) Above 50°C, these inverters must be equipped with a control card cooling fan kit. See catalog.
Summary of Contents for 8I84T200037.01P-1
Page 2: ......
Page 391: ...Accessories ACOPOSinverter P84 User s Manual 2 10 391 4 7 2 Installation 8I0XF084 020 1...
Page 392: ...Accessories 392 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 030 1...
Page 393: ...Accessories ACOPOSinverter P84 User s Manual 2 10 393 8I0XF084 040 1...
Page 394: ...Accessories 394 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 050 1...
Page 395: ...Accessories ACOPOSinverter P84 User s Manual 2 10 395 8I0XF084 0x0 1...
Page 400: ...Accessories 400 ACOPOSinverter P84 User s Manual 2 10...