Programming guidelines
ACOPOSinverter P84 User's Manual 2.10
179
2.8.9.6 Use of analog output AO1 as a logic output
Analog output AO1 can be used as a logic output, by assigning DO1. In this case, the state 0 of this output
corresponds to the AO1 min. value (0 V or 0 mA, for example), and when set to 1 to the AO1 max. value (10 V
or 20 mA, for example).
The electrical data of this analog output remains unchanged; they differ from the data of the logic outputs. Make
sure that these are compatible with the actual application.
[DO1] (dO1-)
Code
Name/Description
Setting range
Factory settings
dO1-
[DO1]
dO1
[DO1]
[No]
(nO)
Identical with R1 (
see "R1 CONFIGURATION" on page 176
) with the following addition (display only for information purposes, as is selection can
only be configured from the
[APPLICATION FCT.]
(Fun-)
menu):
bLC
[BRAKE LOGIC]
(bLC)
: Control braking contactor
LLC
[Line contactor assign]
(LLC)
:Control line contactor
OCC
[Mot. cont.]
(OCC)
: Control downstream motor contactor
EbO
[End wind.]
(EbO)
: End of winding ("Traverse control" function)
tSY
[Sync Wobble]
(tSY)
: Synchronization "counter wobble"
dCO
[DC load]
(dCO)
: Control pre-charge contactor DC bus
dO1d
[DO1 delay time]
0 to 60000 ms
1)
0
For the assignments
[no fault]
(FLt)
,
[BRAKE LOGIC]
(bLC)
,
[Mot. cont.]
(OCC)
,
[DC load]
(dCO)
and
[Assign line cont]
(LLC)
the delay is
not adjustable and remains at 0.
The status change is only effective after the configured time as soon as the information is TRUE.
dO1S
[DO1 active at]
[1]
(POS)
Configuration of the function logic:
POS
[1]
(POS)
: State 1 when the information is TRUE.
nEG
[0]
(nEG)
: State 0 when the information is TRUE.
For the assignments
[no fault]
(FLt)
,
[BRAKE LOGIC]
(bLC)
,
[DC load]
(dCO)
and
[assign line cont]
(LLC)
the configuration
[1]
(POS)
cannot
be changed.
dO1H
[DO1 holding time]
0 to 9999 ms
0
For the assignments
[no fault]
(FLt)
,
[BRAKE LOGIC]
(bLC)
,
[DC load]
(dCO)
and
[assign line cont]
(LLC)
the hold time is not adjustable
and remains at 0.
The status change is only effective after the configured time as soon as the information is UNTRUE.
1)
0 to 9999 ms then 10 to 60 s on the integrated display terminal.
Summary of Contents for 8I84T200037.01P-1
Page 2: ......
Page 391: ...Accessories ACOPOSinverter P84 User s Manual 2 10 391 4 7 2 Installation 8I0XF084 020 1...
Page 392: ...Accessories 392 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 030 1...
Page 393: ...Accessories ACOPOSinverter P84 User s Manual 2 10 393 8I0XF084 040 1...
Page 394: ...Accessories 394 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 050 1...
Page 395: ...Accessories ACOPOSinverter P84 User s Manual 2 10 395 8I0XF084 0x0 1...
Page 400: ...Accessories 400 ACOPOSinverter P84 User s Manual 2 10...