Programming guidelines
ACOPOSinverter P84 User's Manual 2.10
265
2.8.11.21.2 Switching of a motor at the inverter output
Switching in the output is possible at any time. When switching on the running motor (inverter released), the motor
is captured in its current speed and brought back to the desired speed in accordance with the ramp-up time.
For this application, function "Capture in run" (
see "CATCH ON THE FLY (FLr-)" on page 290
) must be configured
and the function for managing an existing motor protection must be enabled.
Typical applications:
•
Safety shutdown at the inverter output
•
Bypass function
•
Operation motors connected parallel
For new installations it is recommended to use the safety function "power removal".
Note:
•
The control of the motor protection must be synchronized with a stop command in the freewheel
stop of the converter on e.g. a logic input/ POWERLINK.
•
Set the parameter
[Output phase loss]
(OPL)
to
[Outp. switch]
(OAC)
, if you are using an output
contactor.
t1
t2
ACOPOSinverter P84
M
KM1
N
1
KM1 0
t
t
T1: Opening time of the KM1 (motor in freewheel stop)
t2: Ramp-up according to ramp
N: Speed
Example: Loss of output protection
Summary of Contents for 8I84T200037.01P-1
Page 2: ......
Page 391: ...Accessories ACOPOSinverter P84 User s Manual 2 10 391 4 7 2 Installation 8I0XF084 020 1...
Page 392: ...Accessories 392 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 030 1...
Page 393: ...Accessories ACOPOSinverter P84 User s Manual 2 10 393 8I0XF084 040 1...
Page 394: ...Accessories 394 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 050 1...
Page 395: ...Accessories ACOPOSinverter P84 User s Manual 2 10 395 8I0XF084 0x0 1...
Page 400: ...Accessories 400 ACOPOSinverter P84 User s Manual 2 10...