5.8 VERIFYING DATA EXCHANGE WITH RSLOGIX 5000
At this point, communication between the BIS M-626 and the PLC should be properly
configured and a connection established. You can verify the exchange of information
between devices using RSLogix 5000.
Figure 52 - RSLogix 5000
5.8.1
Industrial Ethernet (IND)
Handshaking
To ensure that messages to and from the BIS M-626 are properly delivered and received, a
handshaking mechanism has been implemented that uses a pair of dedicated words in the
exchange. The first two words in each
Controller Tag
are dedicated to handshaking.
When new information is generated, the producing device (
Data Producer
) will increment a
counter in one of the
Controller Tags
. After identifying the new data, the consuming device
(
Data Consumer
) will copy that same counter value to a different Controller Tag location,
which lets the Data Producer know that the information has been processed by the Data
Consumer.
WRITE TAG (where responses are written by the Cobalt)
EMS_Write1 [0] =
(2)
the Cobalt copies counter here to ACK
EMS_Write1 [1] =
(3)
the Cobalt increments this counter to signal response available
EMS_Write1 [2] = Data Size
EMS_Write1 [3-102] = Data
READ TAG (where commands are retrieved by the Cobalt)
EMS_Read1 [0] =
(4)
PLC copies the counter here to ACK the response
EMS_Read1 [1] =
(1)
PLC increments this counter after writing a command
EMS_Read1 [2] = Data Size
EMS_Read1 [3-102] = Data
Summary of Contents for BIS M-370-000-A02
Page 1: ......
Page 2: ......
Page 3: ......
Page 7: ......
Page 16: ...9 BIS M 371 000 A01 BIS M 372 000 A01 BIS M 373 000 A01 BIS M 370 000 A02 Figure G...
Page 17: ...10...
Page 21: ...BIS M 62_ MANUAL 14 1...
Page 60: ...INSTALLATION 53 2...
Page 77: ...BIS M 62_ MANUAL 70 4...
Page 101: ...BIS M 62_ MANUAL 94 5...
Page 103: ...BIS M 62_ MANUAL 96 6 The HTTP Server Main Page will be displayed...
Page 126: ...DEVICENET INTERFACE 119 8...
Page 185: ...BIS M 62_ MANUAL 178 10...
Page 188: ...RFID OPERATING PRINCIPLES 181 11...