BIS M-62_ MANUAL
78
5
5. For the
PLC Slot Number,
enter a value between 0 and 255. The PLC Slot Number
indicates the location in your PLC rack where the controller module is installed
(normally slot 0 for ControlLogix).
6. In the
Read Delay
field, enter a value between 0 and 6000. This number specifies (in
10ms “ticks”) how frequently the BIS M-626 will poll the PLC for the presence of new
data. (
Note: a value of 6000 = 60 seconds; zero = disable
).
7.
In the column labeled “
Enable Node,
” place a check in the box for
Node 01.
Other
Nodes listed on this page are not supported by the BIS M-626
–IND.
8.
Write Size:
Enter a value between 1 and 100 (or 0 to disable) for the
Write Size.
The
Write Size represents the maximum number of 2-
byte “words” that the BIS M-626 will
attempt to write to PLC memory during a single write cycle.
(Note: to accommodate
message handshaking overhead, the actual data size required by the PLC is three
words larger than the value specified in this field).
9.
Write Tag Name:
For
ControlLogix
systems, specify a
Write Tag Name
that is 40
characters or less (for example
EMS_WRITE1,
for Node 01). The Write Tag Name is
a user defined description or title for the area of memory in the PLC where host-
bound data will be written for the BIS M-626. (
Note: the Write Tag Name is not to be
confused with writing to an RFID transponder, which i
s often referred to as “writing to
a tag”).
OR
Write Tag Name:
For
PLC5E, SLC5/05 and MicroLogix
systems, enter the
PCCC
File Number and Offset
(for example
N7:0
) in the
Write Tag Name
field. Together
these values identify the location in the PLC’s Status File where host-bound data will
be written for the BIS M-626.
10.
Read Size:
Enter a value between 1 and 100 (or 0 to disable)
for the
Read Size.
The
Read Size represents the maximum number of 2-
byte “words” that the BIS M-626 will
attempt to retrieve from PLC memory during a single read cycle.
(Note: to
accommodate message handshaking overhead, the actual data size required by the
PLC is three words larger than the value specified in this field).
11.
Read Tag Name:
For
ControlLogix
systems, specify a
Read Tag Name
that is 40
characters or less (for example
EMS_READ1,
for Node 01). The Read Tag Name is a
user defined description or title for the area of memory in the PLC from which the BIS
M-626 will retrieve data.
OR
Read Tag Name:
For PLC5E, SLC5/05 and MicroLogix systems enter the
PCCC File
Number and Offset
in the Read Tag Name field. Together these values indicate the
location in the PLC’s Status File from which the BIS M-626 will retrieve data.
12. After entering the proper information for Node 01, click the
Save Settings
button
located at the bottom of the page.
Summary of Contents for BIS M-370-000-A02
Page 1: ......
Page 2: ......
Page 3: ......
Page 7: ......
Page 16: ...9 BIS M 371 000 A01 BIS M 372 000 A01 BIS M 373 000 A01 BIS M 370 000 A02 Figure G...
Page 17: ...10...
Page 21: ...BIS M 62_ MANUAL 14 1...
Page 60: ...INSTALLATION 53 2...
Page 77: ...BIS M 62_ MANUAL 70 4...
Page 101: ...BIS M 62_ MANUAL 94 5...
Page 103: ...BIS M 62_ MANUAL 96 6 The HTTP Server Main Page will be displayed...
Page 126: ...DEVICENET INTERFACE 119 8...
Page 185: ...BIS M 62_ MANUAL 178 10...
Page 188: ...RFID OPERATING PRINCIPLES 181 11...