PROFINET INTERFACE
169
10
10.3 DATA EXCHANGE
The Master Profinet is usually a PLC (Siemens S7 or others) but it could be a PC based
device as well. The Profinet Controller is always Slave in the Profinet network.
PLC
RFID
Controller
RFID
Controller
RFID
Controller
RFID
Controller
RFID
Controller
Profinet Network
Profinet Master
Profinet Slaves
Profinet Slaves
Figure 73 - Profinet IO Network Diagram
Basically two shared memory areas (Exchange Areas) are used to exchange information
between the SLAVE and the MASTER, both devices provide information to each other.
INPUT
AREA
OUTPUT
AREA
PLC
BIS M-628-075-
Write
Read
Write
Read
Exchange Areas
Master
Slave
Figure 74 - Profinet Communication
– Data Exchange Areas Diagram
Input and Output areas always refer to the Master: this means that the Controller writes to
the Input buffer and the PLC writes to the Output buffer.
The dimension of the exchange areas can be set to different values by the PLC through the
GSD file: the Profinet Controller allows up to
248 bytes as a combined total of the Input
and
Output Areas
.
NOTE
For
further
information
regarding
Fieldbus
interfacing
including
downloadable
support
files,
go
to
the
HMS
website
at
http://www.anybus.com, choose the link to the support page, select the
Anybus-CompactCom product type
and then your
network type
.
Summary of Contents for BIS M-370-000-A02
Page 1: ......
Page 2: ......
Page 3: ......
Page 7: ......
Page 16: ...9 BIS M 371 000 A01 BIS M 372 000 A01 BIS M 373 000 A01 BIS M 370 000 A02 Figure G...
Page 17: ...10...
Page 21: ...BIS M 62_ MANUAL 14 1...
Page 60: ...INSTALLATION 53 2...
Page 77: ...BIS M 62_ MANUAL 70 4...
Page 101: ...BIS M 62_ MANUAL 94 5...
Page 103: ...BIS M 62_ MANUAL 96 6 The HTTP Server Main Page will be displayed...
Page 126: ...DEVICENET INTERFACE 119 8...
Page 185: ...BIS M 62_ MANUAL 178 10...
Page 188: ...RFID OPERATING PRINCIPLES 181 11...