Control Wiring 5-1
MN767S
Chapter 5
Control Wiring
5.1 Control Board Connections
Analog and Digital input and output connections are made at the Control Wiring Terminals shown in Figure 5-1.
Control wire connections can be made using shielded twisted pair #18 AWG (0.8mm2) wire minimum. The cable must also
have an overall shield and not exceed 100 feet (30m) in length. Control wire cables must be separated from power wiring.
Separate parallel runs of control cables and power cables by at least 3”. Cross power wires at right angles only. Insulate or
tape ungrounded end of shields to prevent contact with other conductors or ground.
Figure 5-1 Control Terminals
Frame B
1
2
3
4
5
6
7
8
9
10
11
Control Terminals
Tightening Torque =
4.4 lb-in (0.5 Nm)
Table 5-1 Control Terminal Descriptions
Terminal
Signal Description
1
+24VDC (@ 100mA)
2
Digital In1 (8-30VDC)
3
Digital In2 (8-30VDC / Digital Output 3 (24V, 10mA max.)
4
Digital In3 (8-30VDC) / Analog In2 (0-10VDC, 0-20mA or 4-20mA)
5
+24VDC (@ 100mA) Reference for Potentiometer (1kohm minimum)
6
Analog In1 (0-10VDC, 0-20mA or 4-20mA) / Digital In4 (8-30VDC)
7
Common (terminals 7 & 9 are connected)
8
Analog Output (0-10VDC @ 20mA max.) / Digital Output (0-24VDC @ 20mA max.)
9
Common (terminals 7 & 9 are connected)
10
Relay Common
11
Relay N.O. Contact (rated 250VAC@6A; 30VDC@5A)
Summary of Contents for VS1STS Series
Page 1: ...10 11 Installation Operating Manual MN767S VS1STS AC Microdrive ...
Page 6: ...iv MN767S ...
Page 28: ...5 8 Control Wiring MN767S ...
Page 50: ...8 2 Customizing Your Application MN767S ...
Page 54: ...9 4 Troubleshooting MN767S ...
Page 56: ...A 2 Technical Specifications MN767S ...
Page 68: ...D 2 Options and Kits MN767S ...