5-4 Control Wiring
MN767S
P1-08
Digital In 1
(Term 2)
Digital In 2
(Term 3)
Digital In 3
(Term 4)
Analog Input 1
(Term 6)
11
Open: Stop
Open: Bipolar Analog
Speed Ref
Open: Trip
Bipolar Analog Input 1
Closed: Run
Closed: Preset Speed 1
Closed: No Trip
12
Open: Stop
Open: Preset Speed 1
Open: Trip
Bipolar Analog Input 1
Closed: Run
Closed: Bipolar analog
speed ref
Closed: No Trip
13
Normally Open (NO)
Normally Closed (NC)
Open: Bipolar analog speed ref
Bipolar Analog Input 1
Momentarily Close
to Run
Momentarily Open to
Stop
Closed: Preset Speed 1
14
Normally Open (NO)
Normally Closed (NC)
Normally Open (NO)
Bipolar Analog Input 1
Momentarily Close to
Run Fwd
Momentarily Open to
Stop
Momentarily Close to Run Rev
15
Open: Stop
Open: Forward
Open: Decel Ramp 1 (P1-11)
Bipolar Analog Input 1
Closed: Run
Closed: Reverse
Closed: Decel Ramp 2 (P2-25)
16
Open: Stop
Open: Forward
Open: Decel Ramp 1 (P1-11)
Digital Input 4 (Term 6)
Open: Preset Speed 1
Closed: Run
Closed: Reverse
Closed: Decel Ramp 2 (P2-25)
Closed: Preset Speed 2
17
Normally Open (NO)
Normally Closed (NC)
Normally Open (NO)
Digital Input 4 (Term 6)
Open: Preset Speed 1
Momentarily Close to
Run Fwd
Momentarily Open to
Stop
Momentarily Close to Run Rev
Closed: Keypad Speed
18
Open: Stop
Closed: Run
Digital Input 2
(Term 3)
Digital Input 3
(Term 4)
Preset Speed Ref
Digital Input 4 (Term 6)
Open
Open
Preset Speed 1
Open: Preset Speed
Closed
Open
Preset Speed 2
Open
Closed
Preset Speed 3
Closed: Keypad Speed
Closed
Closed
Preset Speed 4
19
Open: Stop
Open : Bipolar Analog 1
Speed Ref
Analog Input 2
Bipolar Analog Input 1
Closed: Run
Closed : Analog Input 2
Speed Ref
20
Open: Stop
Digital Output:
Open: Bipolar Analog Speed Ref
Bipolar Analog Input 1
Closed: Run
Drive Healthy = +24V
Closed: Preset Speed 1
21
Open: Stop
Digital Output:
Open: Forward
Bipolar Analog Input 1
Closed: Run
Drive Healthy = +24V
Closed: Reverse
22
Open: Stop
Digital Output:
Open: Trip
Bipolar Analog Input 1
Closed: Run
Drive Healthy = +24V
Closed: No Trip
Notes:
Negative Preset Speeds will be inverted if Run Reverse is selected.
The external trip input can be used to connect a motor thermistor between terminals 1 and 4.
When P1-07 = 0, P2-01 = 4 and P4-06 < > 2, Analog Input 2 is used for the speed reference.
When P1-07 = 0, P2-01 = 4 and P4-06 = 2, Bipolar Analog Input 1 is used for the speed reference and Analog Input 2 becomes
the torque reference.
Table 5-3 Parameter P1-08 Control of Digital Inputs when P1-07=0 Continued
Summary of Contents for VS1STS Series
Page 1: ...10 11 Installation Operating Manual MN767S VS1STS AC Microdrive ...
Page 6: ...iv MN767S ...
Page 28: ...5 8 Control Wiring MN767S ...
Page 50: ...8 2 Customizing Your Application MN767S ...
Page 54: ...9 4 Troubleshooting MN767S ...
Page 56: ...A 2 Technical Specifications MN767S ...
Page 68: ...D 2 Options and Kits MN767S ...