Using the Keypad 6-1
MN767S
Chapter 6
Using the Keypad
6.1 Keypad Components
This chapter provides an overview of the integrated keypad and how to use it to program the VS1STS drive. The controls are
shown in Table 6-1.
Table 6-1 Operator Interface Description
Key
Name
Description
Display
6 Digit seven segment display. Display of parameter
numbers, values, error messages and other information.
Start
Starts motor if Direction command and Speed reference are
set. Only active if P1-07 is set to allow keypad control and
when P2-19 is not set for 2 or 3. Programmable to change
the motor direction if pressed while running.
Stop / Reset
Stops the drive when in Keypad mode only. Active when
P1-07=1 or 2 and when P2-19 is not set to 2 or 3. Resets
any active faults, if fault condition has been cleared.
Enter / Program
Momentarily press to view available displays. Pressing and
holding the ENT Key for approximately 2 Seconds or more
will enter the programming mode or escape back out of the
programming mode.
Increase
During operation increases the speed reference. (Active in
keypad mode). Pressing for a period of time will increase
the reference value rate of change. In edit mode, navigates
between parameters and increments parameter values.
Decrease
During operation decreases the speed reference. (Active in
keypad mode). Pressing for a period of time will increase
the reference value rate of change. In edit mode, navigates
between parameters and decrements parameter values.
6.2 Changing Parameters
To change a parameter value press and hold the
ENT/PROG key for > 2 seconds while the drive displays
.
The display changes to
, indicating parameter 01. Press and release the ENT/PROG key to display the value of this
parameter.
Use the
UP and
DOWN arrow keys to change to the required value. Press and release the ENT/PROG key
once more to store the change. Press and hold the ENT/PROG key for > 2 second to return to operational mode. The display
shows
if the drive is stopped or the real-time information (for example speed) if the drive is running.
6.3 Reset Factory Default Settings
Press the UP, DOWN,
STOP and
START keys simultaneously for > 2 seconds. The display
shows
indicating the drive has reset itself to factory default parameters. Press the STOP button to acknowledge and
reset the drive.
Summary of Contents for VS1STS Series
Page 1: ...10 11 Installation Operating Manual MN767S VS1STS AC Microdrive ...
Page 6: ...iv MN767S ...
Page 28: ...5 8 Control Wiring MN767S ...
Page 50: ...8 2 Customizing Your Application MN767S ...
Page 54: ...9 4 Troubleshooting MN767S ...
Page 56: ...A 2 Technical Specifications MN767S ...
Page 68: ...D 2 Options and Kits MN767S ...