Control Wiring 5-3
MN767S
5.3 Analog and Digital Input Configurations
Parameters P-07 and P-08 can be set to allow various operating modes. Following are settings for these parameters.
5.3.1 Terminal Strip Mode (P1-07 = 0)
Table 5-3 Parameter P1-08 Control of Digital Inputs when P1-07=0
P1-08
Digital In 1
(Term 2)
Digital In 2
(Term 3)
Digital In 3
(Term 4)
Analog Input 1
(Term 6)
0
Open: Stop
Open: Bipolar Analog
Speed Reference
Open: Preset Speed 1
Bipolar Analog Input 1
Closed: Run
Closed: Preset Speed
Reference
Closed: Preset Speed 2
1
Open: Stop
Open: Preset Speed 1
Open: Preset Speed 1/2
Digital Input 4 (Term 6)
Open: Preset Speed 1/2/3
Closed: Run
Closed: Preset Speed 2
Closed: Preset Speed 3
Closed: Preset Speed 4
2
Open: Stop
Closed: Run
Digital Input 2
(Term 3)
Digital Input 3
(Term 4)
Digital Input 4
(Term 6)
Speed Set point
Open
Open
Open
Preset Speed 1
Closed
Open
Open
Preset Speed 2
Open
Closed
Open
Preset Speed 3
Closed
Closed
Open
Preset Speed 4
Open
Open
Closed
Preset Speed 5
Closed
Open
Closed
Preset Speed 6
Open
Closed
Closed
Preset Speed 7
Closed
Closed
Closed
Preset Speed 8
3
Open: Stop
Open: Forward
Open: Bipolar Analog Ref
Bipolar Analog Input 1
Closed: Run
Closed: Reverse
Closed: Preset Speed 1
4
Open: Stop
Open: Forward
Analog Input 2
(Speed Reference)
Bipolar Analog Input 1
(Torque reference)
Closed: Run
Closed: Reverse
5
Open: Stop
Closed: Run
Open: Forward
Closed: Reverse
Digital Input 3
(Term 4)
Digital Input 4
(Term 6)
Speed Set point
Open
Open
Preset Speed 1
Closed
Open
Preset Speed 2
Open
Closed
Preset Speed 3
Closed
Closed
Preset Speed 4
6
Open: Stop
Closed: Run
Open: Forward
Closed: Reverse
External trip input:
Bipolar Analog Input 1
Open: Trip
Closed: No Trip
7
Open: Stop
Open: Stop
Open: Bipolar Analog Speed Ref
Bipolar Analog Input 1
Closed: Fwd Run
Closed: Rev Run
Closed: Preset Speed 1
8
Open: Stop
Open: Stop
Open: Preset Speed 1
Bipolar Analog Input 1
Closed: Fwd Run
Closed: Rev Run
Closed: Bipolar Analog Speed Ref
9
Open: Stop
Closed: Run Fwd
Open: Stop
Closed: Reverse Run
Digital Input 3
(Term 4)
Digital Input 4
(Term 6)
Preset Speed
Open
Open
Preset Speed 1
Closed
Open
Preset Speed 2
Open
Closed
Preset Speed 3
Closed
Closed
Preset Speed 4
10
Open: Stop
Open: Stop
Open: Trip
Bipolar Analog Input 1
Closed: Forward Run
Closed: Reverse Run
Closed: No Trip
Summary of Contents for VS1STS Series
Page 1: ...10 11 Installation Operating Manual MN767S VS1STS AC Microdrive ...
Page 6: ...iv MN767S ...
Page 28: ...5 8 Control Wiring MN767S ...
Page 50: ...8 2 Customizing Your Application MN767S ...
Page 54: ...9 4 Troubleshooting MN767S ...
Page 56: ...A 2 Technical Specifications MN767S ...
Page 68: ...D 2 Options and Kits MN767S ...