7-4 Parameter Descriptions
MN767S
Par
No.
Description
Range
Units
Default
Explanation
P2-12h
Digital Output Control
High Limit
0.0 to 200.0
%
100.0
With P2-11 = 4 to 6, Digital
Output 1 is set to Logic 1 (+24V
DC) when the value set in P2-
12h is exceeded, and returns to
Logic 0 (0V) when the selected
value reduces below the limit set
in P2-12L
P2-12L
Digital Output Control
Low Limit
0.0 to P2-12h
%
100.0
P2-13
User Relay Output
Function Select
0: Drive Enabled
1: Drive Healthy
2: Motor at Target Speed
3: Motor Speed >0
4: Motor Speed >= Limit
5: Motor Torque >= Limit
6: 2nd Analog Input >= Limit
1
Selects the function assigned to
the relay output.
0: Logic 1 when the drive is
enabled (Running)
1: Logic 1 When no Fault
condition exists on the drive
2: Logic 1 when the motor
speed matches the set point
speed
3: Logic 1 when the motor runs
above zero speed
Options 4 to 6 : the Digital
output is enabled using the
level set in P2-14h and
P2-14L
P2-14h
Relay Output Control
High Limit
0.0 to 200.0
%
100.0
With P2-13 = 4 to 6, the User
Relay Output is set to Logic 1
(+24V DC) when the value set
in P2-14h is exceeded, and
returns to Logic 0 (0V) when the
selected value reduces below
the limit set in P2-12L
P2-14L
Relay Output Control
Low Limit
0.0 to P2-14h
%
100.0
P2-15
Relay Output Mode
0: Normally Open
1: Normally Closed
-
0
Inverts the operating status of
the User Relay
0: Logic 1 = Relay Contacts
Closed
1: Logic 1 = Relay Contacts
Open
The drive must be powered for
the contacts to close
P2-16
Zero Speed Holding
Time
0.0 to 60.0
Seconds
0.2
Determines the time for which
the drive output is held at zero
speed when stopping, before
the drive output is disabled.
P2-17
Start Mode Select
to
5
-
Auto-0
Edge-r: Following Power on or
reset, the drive will not
start if Digital Input 1
remains closed. The
Input must be closed
following a power on or
reset to start the drive.
Auto-0: Following a Power
On or Reset, the drive
will automatically start if
Digital Input 1 is closed.
Auto 1 to 5: Following a Fault,
the drive will make up
to 5 attempts to restart
at 20 second intervals.
The drive must be
powered down to reset
the counter.
Table 7-2 Parameter Group 2 - Extended Parameters
Continued
Summary of Contents for VS1STS Series
Page 1: ...10 11 Installation Operating Manual MN767S VS1STS AC Microdrive ...
Page 6: ...iv MN767S ...
Page 28: ...5 8 Control Wiring MN767S ...
Page 50: ...8 2 Customizing Your Application MN767S ...
Page 54: ...9 4 Troubleshooting MN767S ...
Page 56: ...A 2 Technical Specifications MN767S ...
Page 68: ...D 2 Options and Kits MN767S ...