INTRODUCTION
I-E96-302B
C - 1
APPENDIX C - NTFB01 TERMINATION UNIT CONFIGURATION
INTRODUCTION
The FBS module must use the NTFB01 termination unit to ter-
minate FSK digital smart transmitters on a field bus. All
inputs must be in an FSK digital field bus mode when using
the NTFB01 termination unit. There are no other input types
available when operating in this mode.
CONNECTING INPUTS TO THE NTFB01 TERMINATION UNIT
Figure
shows a simplified circuit diagram of the input sig-
nal path through the field bus termination unit. Figure
shows NTFB01 terminal assignments and Figure
shows
module to termination unit cabling.
Figure C-1. NTFB01 I/O Module Input Circuit
33 V
33 V
33 V
20
Ω
2 0
Ω
43
Ω
62 K
Ω
43
Ω
1 µF
1 µF
FSK+
FSK-
TO FBS
MODULE
CURRENT LIMITING
OR
COMMUNICATION
DISCONNECT
CONTROL
CURRENT LIMITING
OR
COMMUNICATION
DISCONNECT
CONTROL
+24 V
+24 V
FB+
FB-
TP36324B