INTRODUCTION
SPECIFICATIONS
I-E96-302B
1 - 7
SPECIFICATIONS
Table
contains the specifications for the IMFBS01 module.
Table 1-4. Specifications
Property
Characteristic/Value
Power requirements
Operating power
5 VDC, ±5% at 85 mA typical
+15 VDC, ±5% at 25 mA typical
-15 VDC, ±5% at 20 mA typical
Power dissipation
1.1 W typical
Installation category
III for power per ANSI/ISA S:2.01-1994
Operating
Analog inputs
15 independently configured channels
Analog input ranges
4 to 20 mA, 1 to 5 VDC, 0 to 1 VDC,
0 to 5 VDC, 0 to 10 VDC, -10 to +10 VDC
Analog updates
A/D conversions 5 times/sec
FSK digital updates
3 to 10 times/sec (in field bus configuration)
A/D resolution
14 bits with polarity
Analog accuracy
4 to 20 mA 0.1%
1 to 5 VDC 0.1%
0 to 5 VDC 0.1%
0 to 10 VDC 0.1%
±10 VDC 0.1%
0 to 1 VDC 0.25%
Common mode voltage
-12 VDC minimum, +15 VDC maximum
±12 VDC (±1 VDC) input span
±10 VDC (±5 VDC) input span
±5 VDC (±10 VDC) input span
Common mode rejection
90 dB minimum at 60 Hz
Normal mode rejection
70 dB minimum at 60 Hz
Input impedance
Greater than 1 M
Ω
(every channel)
Installation category
III for inputs per ANSI/ISA S:2.01-1994
Environmental
Electromagnetic/radio
frequency interference
No values available at this time. Keep cabinet doors closed. Do not use
communication equipment closer than 2 m (6 ft) from the cabinet.
Ambient temperature
0° to 70°C (0° to 158°F) (noncondensing)
Relative humidity
5% to 95% up to 55°C (131°F)
5% to 45% at 70°C (158°F) (noncondensing)
Atmospheric pressure
Sea level to 3 km (1.86 mi)
Air quality
Noncorrosive
Mounting
Occupies a single slot in a standard INFI 90 module mounting unit (MMU)
Certification
Canadian Standards
Association (CSA)
Certified for use as process control equipment in an ordinary
(nonhazardous) location
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE.