OPERATING PROCEDURES
OPERATION
5 - 2
I-E96-302B
®
OPERATION
Normal operation begins after the FBS module completes the
communication checks of all input channels. During opera-
tion, the function code specifications can be tuned through an
INFI 90 operator interface to make changes in transmitter
operating parameters and calibrate outputs. Refer to the
for more information on func-
tion code 132 (analog input) and function code 133 (smart
transmitter definition).
NOTE: On-line configuration changes which affect the mode of
operation are not supported for function codes 132 and 133. A mode
change (reset) of the MFP or FBS module may be required for
changes to take effect.
Smart transmitter parameters can be viewed or modified using
the handheld Type STT02 smart transmitter terminal. View
only is possible when the FBS module is present and the FBS
channel is on-line. View or modify is possible without the FBS
module present or when the FBS channel is off-line. Figure
shows how the Type STT02 terminal connects to the NTFB01
termination unit.
Figure 5-1. Connecting the Type STT02 Terminal
to the NTFB01 Termination Unit
IMFBS01
NTFB01
NKSL01
P1
P1
TP1 TP2
P2
P3
STT02
TP25164A