![Bailey Infi 90 IMFBS01 Instruction Download Page 32](http://html1.mh-extra.com/html/bailey/infi-90-imfbs01/infi-90-imfbs01_instruction_3481481032.webp)
INSTALLATION
IMFBS01 DIPSWITCH AND JUMPER SETTINGS
I-E96-302B
3 - 5
Termination Unit or Module Installation
Wiring from field devices connect to the INFI 90 system
through terminal blocks on a termination unit or module. If
installing the FBS module in the point-to-point mode, use the
NTAI05 Analog Input Termination Unit (refer to
) or
the NIAI04 Analog Input Termination Module (refer to
).
If installing the FBS module in the field bus mode, the NTFB01
Field Bus Termination Unit must be used. Refer to Appendix C
for information on NTFB01 configuration for field bus termina-
tion. For more information about the termination units or
modules, refer to the instructions listed in Table
.
Installing the IMFBS01 Module
The FBS module inserts into a standard INFI 90 module
mounting unit (MMU) and occupies one slot. To install:
1. Verify the MMU slot assignment for the module.
2. Install a 24-pin dipshunt in all I/O expander bus sockets
(on the MMU backplane) that are between the slot assigned to
the FBS module and the slot assigned to its control module
(MFP/MFC).
3. Connect the hooded end of the cable from the termination
unit or module to the cable opening (on the MMU backplane)
belonging to the FBS slot. Do not force the cable connection to
the MMU backplane. This cable is keyed and should latch into
place when properly installed.
4. Align the module with the guide rails in the module mount-
ing unit. Slide the module into the module mounting unit until
the front panel is flush with the top and bottom of the MMU
frame.
5. Turn the two captive latches ½-turn on the module face-
plate to lock the module in place. To remove the module, turn
the captive latches ½-turn to release the module. Pull on the
module faceplate to remove it from the module mounting unit.
WARNING
Disconnect power before installing dipshunts on the module
mounting unit backplane. Failure to do so will result in contact
with cabinet areas that could cause severe or fatal shock.
AVERTISSEMENT
Interrompez l'alimentation avant d'installer des dipshunts sur
le fond de panier du châssis de montage des modules. Sinon,
tout contact avec cette zone entraîne des risques d'électrocu-
tion sérieuse ou fatale.