![Bailey Infi 90 IMFBS01 Instruction Download Page 49](http://html1.mh-extra.com/html/bailey/infi-90-imfbs01/infi-90-imfbs01_instruction_3481481049.webp)
NTAI05 TERMINATION UNIT CONFIGURATION
CONFIGURING INPUTS
A - 2
I-E96-302B
®
Table A-1. NTAI05 Dipshunt Settings
Application/
Signal Type
Dipshunt
Configuration
Dipshunt
Locations
Connecting
Cable
System powered
4 to 20 mA
XU1 to
XU15
1
NKTU01
Externally powered
4 to 20 mA
Single ended voltage
Differential voltage
2
Above applications:
4 to 20 mA
1 to 5 VDC
0 to 1 VDC
0 to 5 VDC
0 to 10 VDC
±10 VDC
XU17
NOTES:
1. XU16 is not used.
2. FSK not supported at this time.
1
2
3
4
5
6
7
8
16 15 14 13 12 11 10 9
1
2
3
4
5
6
7
8
16 15 14 13 12 11 10 9
1
2
3
4
5
6
7
8
16 15 14 13 12 11 10 9
1
2
3
4
5
6
7
8
16 15 14 13 12 11 10 9
1
2
3
4
5
6
7
8
16 15 14 13 12 11 10 9
TP25171C
Figure A-2. NTAI05 Cable Connections
NKTU01
P1
P1
P3
P2
NTAI05
IMFBS01
TP36308A