COMPONENT DESCRIPTION AND REPLACEMENT
IIMKM02A MULTIBUS KEYBOARD MODULE REPLACEMENT
I-E96-192-5A
6 - 3
jumper to J4 pins one and two to disable the OOT signal. Set
the jumper to J4 pins two and three to enable the OOT signal.
Factory default is to disable OOT on all OIC consoles
NOTE: The two digital outputs are open collector type which sink up
to 250 milliamps. The two digital inputs are rated at up to 250 milli-
amps (future).
Jumper J5 must be set to pins two and three.
Jumpers J6 and J8 are for consoles with the touch screen
option. Setting the jumpers to J6 and J8 pins two and three
disconnects the MKM lead. A cable then connects the touch
screen controller board directly to the CPU port 1.
Jumpers J7 and J9 are reserved for future use and are not
used on the IIOIC42 console.
IIMKM02A MULTIBUS KEYBOARD MODULE REPLACEMENT
The IIMKM02A multibus keyboard module is the only module
used in the IIOIC42 console. The multibus keyboard module
connects the keyboard interface assembly to the CPU.
IIOIC422 Console
In the IIOIC422 model, the MKM board is located in the multi-
bus card cage. Remove the module from the multibus card
cage by following these steps:
1. Open the door on the front of the cabinet and turn off the
main power circuit breaker.
2. Remove the required cables.
3. Loosen (do not remove) the two screws in the left and right
card retaining brackets.
4. Slide the left and right card retaining brackets out of the
way to permit the module removal tabs on the card to pass.
5. To unseat a module, lift the module removal tabs.
6. Carefully slide the module out of the multibus card cage.
7. Check the jumper settings on the new module before
assembling into the card cage.
CAUTION
Failure to turn off the main power circuit breaker before remov-
ing or inserting modules into the card cage may result in
equipment failure.
ATTENTION
Si l'on omet d'eteindre l'interrupteur du circuit d'alimentation
principal avant de retirer les cartes ou de les inserer dans le
porte-cartes, l'equipment pourrait faire default.