![Bailey 40 Series Hardware Manual Download Page 87](http://html1.mh-extra.com/html/bailey/40-series/40-series_hardware-manual_3458780087.webp)
COMPONENT DESCRIPTION AND REPLACEMENT
OPERATOR INTERFACE DEVICES
6 - 24
I-E96-192-5A
®
2. Label and disconnect all cables going to the back of the
monitor.
3. Open the rear door above the air conditioner. Remove the
two screws fastening the monitor mounting tray to the support
rails.
4. Slide the monitor out of the cabinet. The monitor weighs
about 27 kg (60 lbs). Be sure it is well supported.
5. Before installing a new monitor, make certain the resistor
switches are set to
resistor
to insure that the termination is
set for 75 ohms and that the VGA sync switch is set to
GRN
IIOIC424 PANEL MOUNTED MODEL
To remove a monitor from an IIOIC424 panel mounted console:
1. Make certain the power to the console is off.
2. Refer to
on panel mount installation for proce-
dures to remove the bezel.
3. Label and disconnect all cables to or from the monitor.
4. Slide the monitor out of the panel. The monitor weighs
about 27 kg (60 lbs). Be sure it is well supported.
5. Before installing a new monitor, make certain the resistor
switches are set to
resistor
to insure that the termination is
set for 75 ohms and that the VGA sync switch is set to
GRN
MONITOR ASSEMBLY
1. Plug the monitor cable into the monitor port on the back of
the CPU.
2. Connect the red, green and blue cable plugs to the corre-
sponding connectors on the back of the monitor. Use only sup-
plied cables because of length limitations.
3. Plug the monitor power line into the proper socket on the
back of the CPU.
Refer to
to locate the appropriate cable connection
drawing.