![Bailey 40 Series Hardware Manual Download Page 63](http://html1.mh-extra.com/html/bailey/40-series/40-series_hardware-manual_3458780063.webp)
MAINTENANCE
STANDARD PREVENTIVE MAINTENANCE PROCEDURES
5 - 6
I-E96-192-5A
®
Checking and Inspecting Power Entry Panel
The system must be shut down to perform this maintenance
task.
1. Check the tightness of all power wiring screws within the
console. Torque all screws connected to AC power to 1.58 New-
ton meters (14 in-lbs).
2. Inspect and clean the power entry panel and DC distribu-
tion board connections.