118
Installing the Avaya S8700 Media Server with an Avaya G650 Media Gateway
December 2003
The single-phase, 4-wire, 120/240 VAC supplying 208 — 240 VAC can supply 60 Hz power to the AC
load.This source has 2 hot wires, 1 ground wire, and 1 neutral wire (J58890CE).
Either of these power sources can supply 50 Hz power to the AC load:
•
Non-US 5-wire, Y, 220/380 VAC. This source has 3 hot wires, 1 neutral wire, and 1 ground wire.
•
Non-US Delta, 4-wire, 220 or 240 VAC. This source has 3 hot wires and 1 ground wire (describes
the power sources and required AC input power).
Grounding an AC-powered media gateway (J58890CE)
Grounding is relatively simple for an AC-powered media gateway. Basically, the media gateways connect
to the single-point ground terminal block located at either the AC load center or to a separate single-point
ground block wired to the AC load center (or optional AC protector media gateway).
•
The approved ground wire must be a green (or green with yellow stripe), 6 AWG (#40) (16 mm
2
),
copper, stranded wire.
•
Bond all approved grounds at the single-point ground to form a single grounding electrode
system.
Grounding an AC load center 50 feet (15.2 meters) or less from media gateway
1
At the bottom rear of the first media gateway, connect a 6 AWG (#40) (16 mm
2
) media gateway
GROUND wire to the media gateway ground terminal block. See
Figure 26, Typical media
gateway grounding wiring diagram,
on page 108.
2
Route the media gateway GROUND wire to the single-point ground block at the AC load center
and connect.
3
At the bottom rear of the next media gateway (if provided), connect a 6 AWG (#40) (16 mm
2
)
media gateway GROUND wire to the media gateway ground terminal block.
4
Route the media gateway GROUND wire to the single-point ground block at the AC load center
and connect.
NOTE:
If the media gateway is located remotely (in a separate room or building), connect the
media gateway GROUND wire to an approved ground.
5
Repeat connecting each media gateway to the single-point ground block.
Table 7: AC power sources and plug type
Power distribution unit
Power sources
Power input
AC power distribution
(J58890CE) media gateway
Single-phase 120 VAC with
neutral
Single-phase 240 VAC with
neutral, or single phase of 3-
phase, 208 VAC with neutral
120 VAC, 60 Hz NEMA 5-
50R
208-240 VAC, 60 Hz
NEMA L14-30R