Installing the Avaya S8700 Media Server with an Avaya G650 Media Gateway
99
December 2003
Figure 19: Typical media gateway grounding wiring diagram
Connecting remote power off cable, if required
Figure 20, Remote power off cable connections —
Part 1,
on page 100 shows the location of the Remote Power Off (RPO) cable. The opposite end of the
cable connects to the Emergency Power Off (EPO) switch located for the equipment room.
Even though the equipment room EPO switch disconnects main AC power to the equipment room, it
cannot disconnect the battery power from the J58890CH. An auxiliary set of contacts inside the EPO are
used for this function.
1
Plug the RPO cable into the connector shown in
Figure 21, Remote power off cable connections
— Part 2,
on page 101.
2
Route the opposite end of the wires to the EPO switch. The opposite end of the RPO cable
connects to the internal relay.
NOTE:
The EPO switch and the auxiliary contacts (inside the EPO switch assembly) are
customer-provided.
Figure notes
1
Media Gateway
2
Media Gateway Ground Terminal
Block
3
6 AWG (#40) (16 mm
2
) Media
Gateway GROUND Wire
4
Single-Point Ground Block
5
6 AWG (#40) (16 4 mm
2
) Ground Wire to
Approved Ground
6
AC Load Center Single-Point Ground
7
Approved Ground
8
Over 50 ft. (15.2 m)