120
Installing the Avaya S8700 Media Server with an Avaya G650 Media Gateway
December 2003
4
At the next (if provided) DC Power media gateway, connect a 6 AWG (#40) (16 4 mm
2
) media
gateway GROUND wire to the media gateway ground terminal block GROUND DISCHARGE
bar.
5
Route the media gateway GROUND wire to first media gateway and connect to the single-point
ground block and connect block.
NOTE:
If a media gateway is located remotely (in a separate room or building), route the media
gateway GROUND wire to an approved protective ground.
6
Repeat connecting each media gateway to the single-point ground block.
7
Connect a 6 AWG (#40) (16 mm
2
) ground wire to an unused terminal on the single-point ground
block.
8
Route the ground wire to the AC load center ground and connect.
Figure 34: Typical MCC1 Media Gateway grounding wiring diagram
Figure notes
1
Media Gateway
2
Media Gateway Ground Terminal
Block
3
6 AWG (#40) (16 mm
2
) Media
Gateway GROUND Wire
4
Single-Point Ground Block
5
6 AWG (#40) (16 4 mm
2
) Ground Wire to
Approved Ground
6
AC Load Center Single-Point Ground
7
Approved Ground
8
Over 50 ft. (15.2 m)
6
1
3
5
widfspg2 KLC 091603
8
4
2
7