94
Installing the Avaya S8700 Media Server with an Avaya G650 Media Gateway
December 2003
10
Position the media gateway over the holes and adjust the leveling legs until the media gateway is
level.
NOTE:
If the media gateways are supplied with cable ductwork, the media gateways must be level
from front to rear and from side to side. They must be square with respect to each other to
-1/8-inch (0.3-centimeter).
11
Insert the threaded rods through the media gateway bottom and thread into the concrete floor
anchors.
12
Place a 3/8-inch flat washer onto each rod. Thread a 3/8-16 hex nut onto each rod and tighten
securely.
13
Repeat this procedure for each media gateway to be installed (including the auxiliary cabinet, if
required).
Figure 16: Earthquake mounting — raised computer floor
3/8 inch
flat washer
Nut welded
to frame
Leveling
foot
variable
height
4 inches
(10.16 cm)
concrete
subfloor
3/8 - 16
Concrete floor
anchor
3/8 - 16
threaded rod
raised
floor
cab_base CJL 052096