Installing the Avaya S8700 Media Server with an Avaya G650 Media Gateway
83
December 2003
To install a UPS:
1
Connect the UPS to an electrical outlet capable of handling the power requirements of the G650
Media Gateway:
a
100 VAC, 8 amps
b
120 VAC, 8 amps
c
200 VAC, 4 amps
d
220 to 240 VAC, 4 amps
2
Be sure that the G650 Media Gateway is connected to a “nonswitched” or “always on” electrical
outlet on the UPS.
3
Connect and administer the Avaya UPS. (Customers are responsible for connecting and
administering a non-Avaya UPS.)
NOTE:
If an Avaya UPS is wired as recommended, holdover time for each power outage is
1 minute before an automatic shutdown. An UPS can handle any subsequent power outage
based on its total battery capacity.
G650 Media Gateway power switch
!
DANGER
:
The latch on the power supply does not remove power from the G650 Media
Gateway (see
Figure 13, Power supply for the G650 Media Gateway,
on page 84). To
remove the AC power from the 655A, pull the AC power cord from the back of the
G650 Media Gateway. If there are redundant power supplies, you need to pull both
AC power cords from the back of the G650 Media Gateway. To remove DC power,
first locate and switch the external DC circuit breaker to the “off” position and then
disconnect the DC power feed at the back of the G650 Media Gateway.