Add a Switch Node Carrier
Issue 7 November 2003
6-53
555-233-115
Disable Alarm Origination
1. To prevent scheduled daily maintenance from interfering with the update or
upgrade, type change system-parameters maintenance and press
Enter
.
2. If scheduled maintenance has begun, set the
Stop Time
field to 1 minute
after the current time.
or
If scheduled maintenance has not begun, set the
Start Time
field to a
time after the upgrade is completed. For example, if you start the upgrade
at 8:00 p.m. and the upgrade takes 90 minutes, set the
Start Time
field
to 21:30.
!
CAUTION:
If you do not disable Alarm Origination, the system may generate
alarms, resulting in unnecessary trouble tickets.
3. Type neither in the
Alarm Origination to OSS Numbers
field and
press
Enter.
NOTE:
For some software loads, set the
Alarm Origination
Activated
field to n and set the
Cleared Alarm Notification
and
Restart Notification
fields to disable or n before pressing
Enter
.
Check Link Status
1. Type display communication-interface links and press
Enter
. Write down
all enabled links.
2. Type status link number and press
Enter
. Repeat this step for all links.
3. Write down which links are in service.
Save Translations
If standard reliability:
1. Type save translation disk and press
Enter
to take all translation
information in memory and write it to the disk.
If high or critical reliability:
1. Type save translation [spe-a or both] disk and press
Enter
.